BLOWER PERFORMANCE SPECIFICATIONS

GMVC95/AMVC95 Heating Speed Charts

 

 

 

GMVC950905DX*

 

 

 

 

 

GMVC951155DX*

 

 

 

 

 

AMVC950905DX*

 

 

 

 

 

AMVC951155DX*

 

 

 

 

(Rise Range: 30 - 60°F)

 

 

 

(Rise Range: 35 - 65°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

Low Stage

 

High Stage

 

Heating

 

 

Low Stage

 

High Stage

 

Adjust

 

CFM

 

CFM

Rise

Adjust

 

CFM

 

CFM

Rise

Speed

 

 

Speed

 

 

Tap

 

at .1" - .5" w.c.

 

at .1" - .5" w.c.

(°F)

Tap

 

at .1" - .5" w.c.

 

at .1" - .5" w.c.

(°F)

Tap

 

 

Tap

 

 

 

 

ESP

 

ESP

 

 

 

ESP

 

ESP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

 

1013

 

1458

56

 

Minus(-)

 

1107

 

1594

63

A

Normal

 

1125

 

1620

50

A

Normal

 

1230

 

1771

57

 

Plus (+)

 

1238

 

1782

45

 

Plus (+)

 

1353

 

1948

52

 

Minus(-)

 

1076

 

1549

52

 

Minus(-)

 

1139

 

1639

62

B

Normal

 

1195

 

1721

47

B

Normal

 

1265

 

1822

56

 

Plus (+)

 

1315

 

1893

43

 

Plus (+)

 

1392

 

2004

50

 

Minus(-)

 

1139

 

1639

49

 

Minus(-)

 

1170

 

1685

60

C

Normal

 

1265

 

1822

44

C

Normal

 

1300

 

1872

54

 

Plus (+)

 

1392

 

2004

40

 

Plus (+)

 

1430

 

2059

49

 

Minus(-)

 

1202

 

1730

47

 

Minus(-)

 

1202

 

1730

58

D

Normal

 

1335

 

1922

42

D

Normal

 

1335

 

1922

53

 

Plus (+)

 

1469

 

2115

38

 

Plus (+)

 

1469

 

2115

48

1.Units are shipped without filter(s). CFM in chart is without filter(s).

2.All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system.

3.For most cooling applications, about 400 CFM per ton is desirable.

4.The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate.

5.Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only.

6.* Motor CFM minimum.