Goodman Mfg ACVC9/AMVC95, GCVC9/GMVC95 service manual GMVC95/AMVC95 Low Stage Cooling Speed Charts

Models: Goodman 90%-95% Gas Furnace Units ACVC9/AMVC95 GCVC9/GMVC95

1 37
Download 37 pages 20.59 Kb
Page 25
Image 25
GMVC95/AMVC95 Low Stage Cooling Speed Charts

BLOWER PERFORMANCE SPECIFICATIONS

GMVC95/AMVC95 Low Stage Cooling Speed Charts

GMVC950453BX*

AMVC950453BX*

GMVC950704CX*

AMVC950704CX*

GMVC950905CX*

AMVC950905CX*

Cooling

Adjus t

CFM at

Cooling

Adjust

CFM at

Cooling

Adjust

CFM at

 

Speed

.1" - .8"

Speed

.1" - .8"

Speed

.1" - .8"

 

Tap

Tap

Tap

 

Tap

w.c. ESP

Tap

w.c. ESP

Tap

w.c. ESP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

351

 

Minus(-)

351

 

Minus(-)

495

 

A

Norm al

390

A

Norm al

390

A

Norm al

550

 

 

Plus (+)

429

 

Plus (+)

429

 

Plus (+)

605

 

 

Minus(-)

468

 

Minus(-)

468

 

Minus(-)

693

 

B

Norm al

520

B

Norm al

520

B

Norm al

770

 

 

Plus (+)

572

 

Plus (+)

572

 

Plus (+)

847

 

 

Minus(-)

585

 

Minus(-)

644

 

Minus(-)

900

 

C

Norm al

650

C

Norm al

715

C

Norm al

1000

 

 

Plus (+)

715

 

Plus (+)

787

 

Plus (+)

1100

 

 

Minus(-)

702

 

Minus(-)

836

 

Minus(-)

1125

 

D

Norm al

780

D

Norm al

929

D

Norm al

1250

 

 

Plus (+)

858

 

Plus (+)

1022

 

Plus (+)

1375

 

GMVC950905DX*

AMVC950905DX*

Cooling

Adjust

CFM at

Speed

.1" - .8"

Tap

Tap

w.c. ESP

 

 

 

 

 

Minus(-)

468

A

Norm al

520

 

Plus (+)

572

 

Minus(-)

644

B

Norm al

715

 

Plus (+)

787

 

Minus(-)

819

C

Norm al

910

 

Plus (+)

1001

 

Minus(-)

1053

D

Norm al

1170

 

Plus (+)

1287

GMVC951155DX*

AMVC951155DX*

Cooling

Adjust

CFM at

Speed

.1" - .8"

Tap

Tap

w.c. ESP

 

 

 

 

 

Minus(-)

468

A

Norm al

520

 

Plus (+)

572

 

Minus(-)

644

B

Norm al

715

 

Plus (+)

787

 

Minus(-)

819

C

Norm al

910

 

Plus (+)

1001

 

Minus(-)

1053

D

Norm al

1170

 

Plus (+)

1287

1.Units are shipped without filter(s). CFM in chart is without filter(s).

2.All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system.

3.For most cooling applications, about 400 CFM per ton is desirable.

4.The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate.

5.Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only.

6.* Motor CFM minimum.

25

Page 25
Image 25
Goodman Mfg ACVC9/AMVC95, GCVC9/GMVC95 GMVC95/AMVC95 Low Stage Cooling Speed Charts, Blower Performance Specifications