Goodman Mfg ACVC9/AMVC95 GCVC95/ACVC95 Heating Speed Charts, Blower Performance Specifications

Models: Goodman 90%-95% Gas Furnace Units ACVC9/AMVC95 GCVC9/GMVC95

1 37
Download 37 pages 20.59 Kb
Page 28
Image 28
GCVC95/ACVC95 Heating Speed Charts

BLOWER PERFORMANCE SPECIFICATIONS

GCVC95/ACVC95 Heating Speed Charts

GCVC950714CX*

ACVC950714CX*

(Rise Range: 25 - 55°F)

Heating

 

Low Stage

High Stage

 

Adjust

CFM

CFM

Rise

Speed

Tap

at .1" - .5" w.c.

at .1" - .5" w.c.

(°F)

Tap

 

ESP

ESP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

783

1107

55

A

Normal

870

1230

49

 

Plus (+)

957

1353

45

 

Minus(-)

855

1215

50

B

Normal

950

1350

45

 

Plus (+)

1045

1485

41

 

Minus(-)

936

1323

46

C

Normal

1040

1470

41

 

Plus (+)

1144

1617

37

 

Minus(-)

1017

1440

42

D

Normal

1130

1600

38

 

Plus (+)

1243

1760

34

GCVC950915DX*

ACVC950915DX*

(Rise Range: 25 - 55°F)

Heating

 

Low Stage

High Stage

 

Adjust

CFM

CFM

Rise

Speed

Tap

at .1" - .5" w.c.

at .1" - .5" w.c.

(°F)

Tap

 

ESP

ESP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minus(-)

1008

1458

55

A

Normal

1120

1620

50

 

Plus (+)

1232

1782

45

 

Minus(-)

1098

1575

51

B

Normal

1220

1750

46

 

Plus (+)

1342

1925

42

 

Minus(-)

1152

1674

48

C

Normal

1280

1860

43

 

Plus (+)

1408

2046

39

 

Minus(-)

1206

1773

45

D

Normal

1340

1970

41

 

Plus (+)

1474

2167

37

1.Units are shipped without filter(s). CFM in chart is without filter(s).

2.All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system.

3.For most cooling applications, about 400 CFM per ton is desirable.

4.The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate.

5.Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only.

6.* Motor CFM minimum.

28

Page 28
Image 28
Goodman Mfg ACVC9/AMVC95, GCVC9/GMVC95 service manual GCVC95/ACVC95 Heating Speed Charts, Blower Performance Specifications