Goodman Mfg GCVC9/GMVC95, ACVC9/AMVC95 service manual GCVC95/ACVC95 Low Stage Cooling Speed Charts

Models: Goodman 90%-95% Gas Furnace Units ACVC9/AMVC95 GCVC9/GMVC95

1 37
Download 37 pages 20.59 Kb
Page 30
Image 30
GCVC95/ACVC95 Low Stage Cooling Speed Charts

BLOWER PERFORMANCE SPECIFICATIONS

GCVC95/ACVC95 High (Single) Stage Cooling Speed Charts

GCVC950714CX*

ACVC950714CX*

GCVC950915DX*

ACVC950915DX*

Cooling

Adjust

CFM at

Cooling

Adjust

CFM at

Speed

Tap

.1" - .8"

Speed

Tap

.1" - .8"

Tap

w.c. ESP

Tap

w.c. ESP

 

 

 

 

 

 

 

 

 

Minus(-)

594

 

Minus(-)

729

A

Normal

660

A

Normal

810

 

Plus (+)

726

 

Plus (+)

891

 

Minus(-)

747

 

Minus(-)

999

B

Normal

830

B

Normal

1110

 

Plus (+)

913

 

Plus (+)

1221

 

Minus(-)

1017

 

Minus(-)

1287

C

Normal

1130

C

Normal

1430

 

Plus (+)

1243

 

Plus (+)

1573

 

Minus(-)

1314

 

Minus(-)

1674

D

Normal

1460

D

Normal

1860

 

Plus (+)

1606

 

Plus (+)

2046

GCVC95/ACVC95 Low Stage Cooling Speed Charts

GCVC950714CX*

ACVC950714CX*

GCVC950915DX*

ACVC950915DX*

Cooling

Adjust

CFM at

Cooling

Adjust

CFM at

Speed

Tap

.1" - .8"

Speed

Tap

.1" - .8"

Tap

w.c. ESP

Tap

w.c. ESP

 

 

 

 

 

 

 

 

 

Minus(-)

378

 

Minus(-)

504

A

Normal

420

A

Normal

560

 

Plus (+)

462

 

Plus (+)

616

 

Minus(-)

531

 

Minus(-)

666

B

Normal

590

B

Normal

740

 

Plus (+)

649

 

Plus (+)

814

 

Minus(-)

702

 

Minus(-)

828

C

Normal

780

C

Normal

920

 

Plus (+)

858

 

Plus (+)

1012

 

Minus(-)

864

 

Minus(-)

1071

D

Normal

960

D

Normal

1190

 

Plus (+)

1056

 

Plus (+)

1309

1.Units are shipped without filter(s). CFM in chart is without filter(s).

2.All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed. The first task is to determine the proper aiflow for the cooling system.

3.For most cooling applications, about 400 CFM per ton is desirable.

4.The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on rating plate.

5.Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling purposes only.

6.* Motor CFM minimum.

30

Page 30
Image 30
Goodman Mfg GCVC9/GMVC95, ACVC9/AMVC95 GCVC95/ACVC95 Low Stage Cooling Speed Charts, Blower Performance Specifications