SERVICING

DIPSWITCH FUNCTIONS

The MBE air handler motor has an electronic control that contains an eight (8) position dip switch. The function of these dipswitches are shown in Table 1.

Dipswitch Number

Function

1

Electric Heat

2

 

3

N/A

4

Indoor Thermostat

5

Cooling & Heat Pump CFM

6

 

7

CFM Trim Adjust

8

 

 

Table 1

CFM DELIVERY

Tables 2, 2A and 3, 3A show the CFM output for dipswitch combinations 1-2, 5-6 and 7-8.

Electric Heat Operation

Model

Switch 1

Switch 2

CFM

 

OFF

OFF

1,200

MBE1200

ON

OFF

1,000

OFF

ON

800

 

 

ON

ON

600

 

OFF

OFF

1,600

MBE1600

ON

OFF

1,400

OFF

ON

1,200

 

 

ON

ON

1,000

 

OFF

OFF

2,000

MBE2000

ON

OFF

1,800

OFF

ON

1,600

 

 

ON

ON

1,200

 

Table 2

 

Cooling/Heat Pump Operation

 

Model

Switch 5

Switch 6

CFM

 

OFF

OFF

1,200

MBE1200

ON

OFF

1,000

OFF

ON

800

 

 

ON

ON

600

 

OFF

OFF

1,600

MBE1600

ON

OFF

1,400

OFF

ON

1,200

 

 

ON

ON

1,000

 

OFF

OFF

1,600

MBE2000

ON

OFF

1,400

OFF

ON

1,200

 

 

ON

ON

1,000

Table 2A

Dipswitch 1/2 & 7/8

 

 

 

 

 

 

 

 

 

 

 

 

AEPF 1830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

Switch

Switch

 

Emergency

 

Heat Pump

Element

 

Position

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backup

 

With Backup

 

(kw)

 

1

 

 

2

7

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP TO 10

 

OFF

 

OFF

OFF

 

 

OFF

 

 

1100

 

1210

UP TO 10

 

ON

 

OFF

OFF

 

 

OFF

 

 

890

 

935

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

OFF

 

ON

OFF

 

 

OFF

 

 

700

 

770

AEPF3036 / 3137 / 4260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

Switch

Switch

 

Emergency

 

Heat Pump

Element

 

Position

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backup

 

With Backup

 

(kw)

 

1

 

 

2

7

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP TO 20

 

OFF

 

OFF

OFF

 

 

OFF

 

 

2050

 

2150

UP TO 20

 

ON

 

OFF

OFF

 

 

OFF

 

 

1750

 

1835

UP TO 15

 

OFF

 

ON

OFF

 

 

OFF

 

 

1600

 

1680

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP TO 10

 

ON

 

ON

OFF

 

 

OFF

 

 

1200

 

1260

UP TO 10

 

ON

 

ON

OFF

 

 

ON

 

 

1020

 

1070

 

 

 

 

 

 

 

 

Table 3

 

 

 

 

 

 

 

 

 

Dipswitch 5/6 & 7/8

 

 

 

 

 

 

 

 

 

 

 

 

AEPF 1830

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

 

Switch

 

 

 

Indoor Airflow

 

 

Position

 

 

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

6

 

 

7

8

 

 

Cooling

 

Heat Pump

 

 

OFF

 

OFF

 

 

OFF

OFF

 

 

1100

 

 

1100

 

 

ON

 

OFF

 

 

OFF

OFF

 

 

800

 

 

800

 

 

OFF

 

 

ON

 

 

OFF

OFF

 

 

600

 

 

600

 

 

AEPF3036 / 3137 / 4260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch

 

 

Switch

 

 

 

Indoor Airflow

 

 

Position

 

 

Position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

6

 

 

7

8

 

 

Cooling

 

Heat Pump

 

 

OFF

 

OFF

 

 

OFF

OFF

 

 

1800

 

 

1800

 

 

ON

 

OFF

 

 

OFF

OFF

 

 

1580

 

 

1580

 

 

OFF

 

 

ON

 

 

OFF

OFF

 

 

1480

 

 

1480

 

 

ON

 

 

ON

 

 

OFF

OFF

 

 

1200

 

 

1200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

ON

 

 

OFF

ON

 

 

1020

 

 

1020

 

Table 3A

THERMOSTAT “FAN ONLY” MODE

During Fan Only Operations, the CFM output is 30% of the cooling setting.

CFM TRIM ADJUST

Minor adjustments can be made through the dip switch combination of 7-8. Table 4 shows the switch position for this feature.

NOTE: The airflow will not make the decreasing adjustment in Electric Heat mode.

C FM

S w itc h 7

S w itc h 8

+ 1 0 %

O N

O F F

-1 5 %

O F F

O N

Table 4