Goodman Mfg RT6100004R13 manual S-102EVACUATION, S-103CHARGING, Servicing, Evacuation

Models: RT6100004R13

1 69
Download 69 pages 54.01 Kb
Page 51
Image 51
S-102 EVACUATION

SERVICING

EVACUATION WARNING

To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.

Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure, then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.

S-102 EVACUATION

S-103 CHARGING WARNING

REFRIGERANT UNDER PRESSURE!

Failure to follow proper procedures may cause property damage, personal injury or death.

This is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air (non-condensables) and moisture from the system.

Air in a system causes high condensing temperature and pressure, resulting in increased power input and reduced performance.

Moisture chemically reacts with the refrigerant oil to form corrosive acids. These acids attack motor windings and parts, causing breakdown.

The equipment required to thoroughly evacuate the system is a high vacuum pump, capable of producing a vacuum equiva- lent to 25 microns absolute and a thermocouple vacuum gauge to give a true reading of the vacuum in the system

NOTE: Never use the system compressor as a vacuum pump or run when under a high vacuum. Motor damage could occur.

Manual background WARNING

Do not front seat the service valve(s) with the compressor open, with the suction line of the comprssor closed or severely restricted.

1.Connect the vacuum pump, vacuum tight manifold set with high vacuum hoses, thermocouple vacuum gauge and charging cylinder as shown.

2.Start the vacuum pump and open the shut off valve to the high vacuum gauge manifold only. After the compound gauge (low side) has dropped to approximately 29 inches of vacuum, open the valve to the vacuum thermocouple gauge. See that the vacuum pump will blank-off to a maximum of 25 microns. A high vacuum pump can only produce a good vacuum if its oil is non-contaminated.

 

R-22

 

MANIFOLD

LOW SIDE

HIGH SIDE

GAUGE

GAUGE

AND VALVE

AND VALVE

800 PSI RATED HOSES

CHARGING

CYLINDER

AND SCALE

{

 

VACUUM PUMP

 

TO

 

ADAPTER

UNIT SERVICE

 

 

VALVE PORTS

 

 

 

VACUUM PUMP

EVACUATION

3.If the vacuum pump is working properly, close the valve to the vacuum thermocouple gauge and open the high and low side valves to the high vacuum manifold set. With the valve on the charging cylinder closed, open the manifold valve to the cylinder.

4.Evacuate the system to at least 29 inches gauge before opening valve to thermocouple vacuum gauge.

5.Continue to evacuate to a maximum of 250 microns. Close valve to vacuum pump and watch rate of rise. If vacuum does not rise above 1500 microns in three to five minutes, system can be considered properly evacuated.

6.If thermocouple vacuum gauge continues to rise and levels off at about 5000 microns, moisture and non- condensables are still present. If gauge continues to rise a leak is present. Repair and re-evacuate.

7.Close valve to thermocouple vacuum gauge and vacuum pump. Shut off pump and prepare to charge.

S-103 CHARGING

Manual background WARNING

REFRIGERANT UNDER PRESSURE!

*Do not overcharge system with refrigerant.

*Do not operate unit in a vacuum or at negative pressure.

Failure to follow proper procedures may cause property damage, personal injury or death.

51

Page 51
Image 51
Goodman Mfg RT6100004R13 manual S-102EVACUATION, S-103CHARGING, Servicing, Evacuation