TROUBLESHOOTING CHART
COOLING/HP ANALYSIS CHART
|
|
|
| No Cooling |
|
| Unsatisfactory Cooling/Heating |
| System |
|
| |||||||||
Complaint |
|
|
|
|
|
| Operating |
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Pressures |
|
| |
POSSIBLE CAUSE | SYMPTOM | startnotwillSystem | startnotwillFanCond.andComp. | startnotwillfanEvaporator | startnotwillfanCondenser | overloadoncyclesCompressor | warmtoothenandcoolToo dayswarmonenoughcoolNot | toootherscool,tooareasCertainwarm | noisyisCompressor | defrostterminatenotwillUnit | defrostnotwillUnit | pressuresuctionLow | pressureheadLow | pressuresuctionHigh | pressureheadHigh | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
DOTS IN ANALYSIS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Method |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Remedy | |
GUIDE INDICATE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
"POSSIBLE CAUSE" |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power Failure | • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Voltage |
Blown Fuse | • |
| • | • | • |
| • | • |
|
|
|
|
|
|
|
|
|
|
|
| Inspect Fuse Size & Type |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Unbalanced Power, 3PH |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Voltage | |||
• |
|
|
| • |
| • |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Loose Connection |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Inspect Connection - Tighten | |||
• |
| • | • | • | • | • |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Shorted or Broken Wires |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Circuits With Ohmmeter | ||||||
|
|
|
| • | • |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Open Fan Overload |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Continuity of Overload | ||
• |
|
| • | • |
|
|
|
| • |
|
|
|
|
|
|
|
|
|
| ||
Faulty Thermostat |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Continuity of Thermostat & Wiring | ||||
• |
|
| • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Faulty Transformer |
| • | • | • | • | • |
|
|
|
|
|
|
|
|
|
|
|
| Check Control Circuit with Voltmeter | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Shorted or Open Capacitor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Capacitor | |||||
|
| • |
|
|
|
|
|
|
|
|
|
| ♦ |
|
|
|
|
|
| ||
Internal Compressor Overload Open |
|
|
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
| Test Continuity of Overload | ||
Shorted or Grounded Compressor |
|
| • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Motor Windings | |
Compressor Stuck |
|
| • | • |
| • | • | • |
|
|
|
|
| ♦ |
|
|
|
|
|
| Use Test Cord |
Faulty Compressor Contactor |
|
|
| • | • |
|
|
|
|
|
|
|
|
|
|
|
|
| Test Continuity of Coil & Contacts | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Faulty Fan Relay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Test Continuity of Coil And Contacts | |
|
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Open Control Circuit |
|
| • |
|
| • | • |
|
|
|
|
|
|
|
|
|
|
|
| Test Control Circuit with Voltmeter | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Low Voltage |
|
|
| • |
|
|
|
|
|
|
|
|
| • |
|
|
| Test Voltage | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Faulty Evap. Fan Motor |
|
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
| ♦ Repair or Replace | |||
Shorted or Grounded Fan Motor |
|
|
|
|
| • |
| • |
|
|
|
|
|
|
|
| • | Test Motor Windings | |||
Improper Cooling Anticipator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check Resistance of Anticipator | ||
|
|
|
|
|
|
| • | • |
|
|
|
| ♦ |
|
| • | • |
|
| ||
Shortage of Refrigerant |
|
|
|
|
|
|
|
|
|
|
|
|
|
| • | Test For Leaks, Add Refrigerant | |||||
Restricted Liquid Line |
|
|
|
|
|
|
| • | • |
|
|
|
|
|
|
| • | • |
| Remove Restriction, Replace Restricted Part | |
Open Element or Limit on Elec. Heater |
|
|
|
|
|
|
|
| ♦ |
| • | • |
| ♦ |
|
| • |
|
|
| Test Heater Element and Controls |
Dirty Air Filter |
|
|
|
|
|
|
|
| • |
|
|
|
|
|
|
| ♦ Inspect | ||||
Dirty Indoor Coil |
|
|
|
|
|
|
|
| • |
| • | • |
|
|
|
| • |
|
| ♦ Inspect Coil - Clean | |
Not enough air across Indoor Coil |
|
|
|
|
|
|
|
| • |
| • | • |
|
|
|
| • | ♦ | • | ♦ Check Blower Speed, Duct Static Press, Filter | |
Too much air across Indoor Coil |
|
|
|
|
|
| • | • |
| • |
|
|
| • | Reduce Blower Speed | ||||||
Overcharge of Refrigerant |
|
|
|
|
|
|
|
| • |
| ♦ |
|
|
|
| • | Recover Part of Charge | ||||
Dirty Outdoor Coil |
|
|
|
|
|
| • | • |
|
|
|
|
|
|
| ♦ |
|
| • | Inspect Coil - Clean | |
Noncondensibles |
|
|
|
|
|
|
| • |
|
| • |
|
| ♦ |
|
|
|
|
| • | Recover Charge, Evacuate, Recharge |
Recirculation of Condensing Air |
|
|
|
|
|
|
| • | • |
| • | • |
|
|
|
|
|
|
| • | Remove Obstruction to Air Flow |
Infiltration of Outdoor Air |
|
|
|
|
|
| • |
| • | • |
|
|
|
|
|
|
|
| Check Windows, Doors, Vent Fans, Etc. | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Improperly Located Thermostat |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Relocate Thermostat | ||
|
|
|
|
|
|
|
|
| • |
| • |
|
|
|
|
|
|
|
| ||
Air Flow Unbalanced |
|
|
|
|
|
|
|
| • | • |
|
|
|
|
|
|
|
| Readjust Air Volume Dampers | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
System Undersized |
|
|
|
|
|
|
|
|
|
| • | ♦ |
|
|
|
|
|
| Refigure Cooling Load | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Broken Internal Parts |
|
|
|
|
|
|
|
| • |
|
|
|
|
|
| • | • |
| Replace Compressor | ||
Broken Valves |
|
|
|
|
|
|
|
|
|
|
| • |
|
|
|
|
| Test Compressor Efficiency | |||
Inefficient Compressor |
|
|
|
|
|
| • | • | • |
| • |
|
| ♦ |
|
| • | • | • |
| Test Compressor Efficiency |
Wrong Type Expansion Valve |
|
|
|
|
|
| • |
|
|
|
|
|
| • |
| ♦ Replace Valve | |||||
Expansion Device Restricted |
|
|
|
|
|
| • | • | • |
| • |
|
|
|
|
| • | • |
| • | Remove Restriction or Replace Expansion Device |
Oversized Expansion Valve |
|
|
|
|
|
| • | • | • |
| • |
|
|
|
|
| • |
|
| • | Replace Valve |
Undersized Expansion Valve |
|
|
|
|
|
| • |
|
| • |
|
|
|
| • |
| Replace Valve | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Expansion Valve Bulb Loose |
|
|
|
|
|
| • |
| • |
|
|
|
|
|
| • |
|
| Tighten Bulb Bracket | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
Inoperative Expansion Valve |
|
|
|
|
|
|
|
|
|
| • |
|
|
|
|
|
| Check Valve Operation | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Loose |
|
|
|
|
|
| • |
|
|
|
|
|
|
|
|
|
|
|
| Tighten Bolts | |
Faulty Reversing Valve |
|
|
|
|
| • |
|
|
|
|
| ♦ | ♦ | ♦ |
| ♦ | ♦ | ♦ Replace Valve or Solenoid | |||
Faulty Defrost Control |
|
|
|
|
|
|
|
|
|
|
| ♦ | ♦ | ♦ | ♦ | ♦ |
| ♦ Test Control | |||
Faulty Defrost Thermostat |
|
|
|
|
|
|
|
|
|
|
|
|
| ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | ♦ | Test Defrost Thermostat |
Flowrator Not Seating Properly | • |
|
|
|
|
|
|
| • |
|
|
|
|
|
|
|
| • | • |
| Check Flowrator & Seat or Replace Flowrator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
| Cooling or Heating Cycle (Heat Pump) |
|
|
| ♦ Heating Cycle Only (Heat Pump) |
See Service Procedure Ref.