S-105B THERMOSTATIC EXPANSION VALVE

SERVICING

NOTE: The compressor may run backwards (noisy opera- tion) for 1 or 2 seconds at shutdown. This is normal and does not harm the compressor.

S-105A PISTON KIT CHART FOR ASC13, GSC13, VSC13, GSC14, ASH13, GSH13, VSH14, GSH14 UNITS

1.Install gauges and verify that the suction pressure drops while the discharge pressure increases.

2.Listen for normal compressor sound levels. Reverse rota- tion results in elevated or unusual sound levels.

3.Reverse rotation will result in substantially reduced amp draw from tabulated values.

To correct improper rotation, switch any two power supply leads at the outdoor unit contactor.

The 3 phase Scroll Compressors are direction of rotation sen- sitive. They will rotate in either direction depending on the phasing of the power. There is no negative impact on durabil- ity caused by operating 3 phase compressors in reversed rotation. The compressors internal protector will trip, de-en- ergizing the compressor. Continued operation of 3 phase scroll compressors with the rotation reversed will contribute to com- pressor failure. All 3 phase scroll compressors should be checked for correct phase rotation.

Air Conditioners

Orifice

Size

 

G/VSC130181A*

.055

GSC130181B*

.055

G/VSC130241A*

.059

GSC130241C*

 

AC30, ACNF24

.059

AWB24/AWUF24

.059

# All other ARI Matches

.061

G/VSC130301A* / D*

 

GSC130303A*

 

AC36, ACNF30

.065

AWB36, AWUF36

.068

# All other ARI Matches

.065

G/VSC130361A*

 

GSC130363A* / B*

.071

AWB36, AWUF36

.071

# All other ARI Matches

.074

GSC130361B* / F*

.071

G/VSC130421A*

.078

G/VSC130481A

.082

GSC130483A*/ 4A*

.082

G/VSC130601A*

.093

GSC130603A*/ 4A*

.093

ASC130181A*

.055

ASC130241A*

.061

ASC130301A*

.065

ASC130361A*

.071

ASC130421A*

.078

ASC130481A*

.082

ASC130601A*

.093

GSC140181A*

.053

GSC140241A*

.061

GSC140301A*

.067

GSC140361A*

.074

GSC140421A*

.078

GSC140481A*

.084

GSC140601A*

.096

GSC140181B*

.055

GSC140241B*

.062

GSC140301B*

.067

GSC140361B*

.073

GSC140421B*

.080

Heat Pumps

Orifice

Size

 

G/VSH130181A*

.052

GSH130181B*

.055

G/VSH130191A*

.052

G/VSH130241A*

.061

GSH130241B*

.061

G/VSH130251A*

.061

G/VSH130301A*

.068

GSH130301B*

.070

G/VSH130311A*

.065

G/VSH130361A*

.073

GSH1303613A*/1B*

.082

G/VSH130421A*

.082

G/VSH130481A*

.084

GSH1304813A*/ 4A*

.084

G/VSH130601A*

.093

GSH1306013A*/ 4A*

.093

ASH130181A*

.052

ASH130241A*

.062

ASH130301A*

.065

ASH130361A*

.073

ASH130421A*

.082

ASH130481A*

.084

ASH130601A*

.093

GSH140361A*

.076

GSH140421A*

.078

GSH140481A*

.088

S-105B THERMOSTATIC EXPANSION VALVE

The expansion valve is designed to control the rate of liquid refrigerant flow into an evaporator coil in exact proportion to the rate of evaporation of the refrigerant in the coil. The amount of refrigerant entering the coil is regulated since the valve responds to temperature of the refrigerant gas leaving the coil (feeler bulb contact) and the pressure of the refrigerant in the coil. This regulation of the flow prevents the return of liquid refrigerant to the compressor.

The illustration below shows typical heat pump TXV/check valve operation in the heating and cooling modes.