Roof Curb Mounting
Curb Outside Dimensions and Weights
Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.
Factory Supplied Roof Curbs: Roof curbs are Model GKD, which are shipped in a knockdown kit (includes duct adapter) and require field assembly (by others). Assembly instructions are included with the curb.
Install Curb: Locate curb over roof opening and fasten in place. Reference Installation, Unit Weights
SIDE OF UNIT
A
B
C
D
E
BASE
1 INCH INSULATION
and Recommended Roof Openings in this manual. Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper coil drainage and unit operation, it is important that the installation be level. Shim as required to level.
Install Ductwork:
Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.
Set the Unit: Lift |
|
| |
unit to a point directly |
|
| |
above the curb and |
|
| |
duct openings. Guide |
|
| |
unit while lowering |
|
| |
to align with duct |
|
|
|
openings. Roof curbs |
|
| |
fit inside the unit | base. |
|
|
Make sure the unit is |
|
| |
properly seated on the | Set the Unit |
| |
curb and is level. |
|
| |
|
|
| |
Curb Outside Dimensions and Curb Weights (lbs) | |||
Unit Size | L | W | Weight |
104.88 | 51.00 | 310 | |
115.75 | 60.63 | 400 | |
129.88 | 71.50 | 510 | |
148.13 | 90.75 | 720 |
All dimensions are in inches. Weights are for 12 inch high curbs. Roof curb details, including duct locations dimensions are available on the roof curb assembly instructions.
10Model
ROOF CURB
Curb Cap Details for
Curb Cap Dimensions
Unit Size | A | B | C | D | E |
|
|
|
|
|
|
2.00 | 2.00 | 1.00 | 0.88 | 0.75 | |
|
|
|
|
|
|
2.00 | 4.25 | 2.00 | 1.31 | 0.50 | |
|
|
|
|
|
|
2.00 | 4.25 | 2.00 | 1.31 | 0.50 | |
|
|
|
|
|
|
2.00 | 4.25 | 2.00 | 1.31 | 0.50 | |
|
|
|
|
|
|
All dimensions are in inches.