Troubleshooting – Refrigeration Circuit
Symptom | Possible Cause | Corrective Action | |
|
|
| |
| Refrigerant undercharge. | Check pressures and subcooling. | |
|
|
| |
| Blower running backward. | Interchange any two wires from 3 phase | |
| disconnect. | ||
|
| ||
|
|
| |
| Loose blower, pulley or belts. | Check drive pulley alignment, belt tension. | |
|
|
| |
| Low entering air temperature (low load condition). | Check entering air wet bulb conditions. | |
|
|
| |
| Refrigerant leak. | Check system for leaks. Repair leaks and add | |
Low suction | refrigerant. | ||
| |||
pressure |
|
| |
Evaporator dirty or iced up or airflow restricted. | Check defrost system. Clean the coil. | ||
| |||
| Check fan operation. Check airflow. | ||
|
| ||
|
|
| |
| Plugged liquid line | Replace | |
|
|
| |
| Improper suction pressure regulator setting. | Check setting and correct as required. | |
|
|
| |
| Expansion valve defective, superheat too high, or | Adjust valve for proper superheat or replace the | |
| valve too small. | expansion valve if too small or defective. | |
|
|
| |
| Moisture in system. | Reclaim refrigerant, check for leaks, recharge. | |
|
|
| |
| Insufficient refrigerant charge. | Check subcooling, check for leak. Repair leak and | |
| add refrigerant. | ||
|
| ||
|
|
| |
| Defective or improperly adjusted expansion | Check superheating and adjust thermal expansion | |
Low discharge | valve. | valve. | |
pressure |
|
| |
Low suction pressure. | See “Low suction pressure”. | ||
| |||
|
|
| |
| Faulty condenser temperature controls. | Check condenser controls and reset to obtain | |
| desired condensing temperature. | ||
|
| ||
|
|
| |
| Thermostat location or malfunction. | Check thermostat, check heat anticipator setting. | |
|
|
| |
| Improper refrigerant charge. | Check subcooling, verify superheat. | |
|
|
| |
| Defective high or low pressure control. | Check high or low pressure switch. | |
|
|
| |
| Liquid floodback. | Possible tight bearings. | |
|
|
| |
Compressor | Defective expansion valve. | Check thermal expansion valve and superheat. | |
|
| ||
short cycles | Poor air distribution. | Check ductwork for recirculating. | |
| |||
|
|
| |
| High discharge pressure. | See “High discharge pressure”. | |
|
|
| |
| Leaking discharge valves in compressor. | See “High suction pressure”. | |
|
|
| |
| Low airflow at evaporator(s). | Check blower operation and airstream restrictions. | |
|
|
| |
| Incorrect unit selection (oversized). | Contact factory. | |
|
|
|