Greenheck Fan 473501 Troubleshooting - Airflow, Troubleshooting – Unit, Unit #1, Unit #2, Unit #3

Models: 473501

1 40
Download 40 pages 12.86 Kb
Page 29
Image 29
Troubleshooting – Airflow

Troubleshooting – Airflow

The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low, prior to contacting the factory, please determine the following information:

Unit #1

Unit #2

Unit #3

Unit #4

Model Number

Serial Number

Nameplate Information

Voltage

Hertz

Phase

Outdoor Air Fan Amps

Outdoor Air Fan Horsepower

Design Airflow

Outdoor Air

Measured Airflow

Outdoor Air

Measured Data

Blower Rotation

Outdoor Air Fan RPM

Outdoor Air Fan Amp Draw

Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in accordance with SMACNA and AMCA guidelines.

Troubleshooting – Unit

Symptom

Possible Cause

Corrective Action

 

 

 

 

Blown fuse or open circuit breaker.

Replace fuse or reset circuit breaker and check amps.

 

 

 

 

Defective motor or capacitor.

Replace.

 

 

 

Blower fails to

Motor starter overloaded.

Reset starter and check amps.

 

 

operate

Electrical.

Check for On/Off switches. Check for correct supply

 

voltage.

 

 

 

 

 

 

Drive.

Check for broken or loose belts. Tighten loose

 

pulleys.

 

 

 

 

 

 

 

Shorten wiring run to mechanical room or install a

 

Control power (24 VAC) wiring run is too long

relay which will turn unit on/off. Consult Factory for

Motor starters

(resistance should not exceed 0.75 ohms).

relay information. Increase wire gauge size so that

 

resistance is .075 ohms or less.

“chatter” or

 

 

Incoming supply power is less than anticipated.

 

do not pull in

Need to increase supply power or use a special

 

Voltage supplied to starter coil must be within

 

control transformer which is sized for the actual

 

+10% / -15% of nominal voltage stated on the

 

supply power.

 

coil.

 

 

 

 

 

Always have a completed Pre Start-Up Checklist and Unit Start-Up Checklist prior to requesting parts or service information.

Model ERCH-HP Energy Recovery Unit 29