Greenheck Fan 473501 manual Unit Protection Module UPM Fault Indications, Lockout Reset

Models: 473501

1 40
Download 40 pages 12.86 Kb
Page 27
Image 27
Unit Protection Module (UPM) Fault Indications

Unit Protection Module (UPM) Fault Indications

Each unit includes one Unit Protection Module (UPM) printed circuit board and each UPM has two LED indictor lights.

LED

LED Fault Indication

Color

 

Lockout Reset

A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.

Green

Power LED indicates 18-30 VAC present at

the board

 

 

 

 

 

 

 

Dual or

# of

 

 

Single

Status

 

blinks

 

Compressor

 

 

 

 

 

 

 

 

 

 

1

High pressure lockout

 

 

Compressor 1

 

 

 

 

 

 

 

 

 

2

Low pressure lockout

 

 

Compressor 1

 

 

 

 

 

3

High pressure lockout

 

 

Compressor 2

 

 

 

 

 

 

 

 

 

4

Low pressure lockout

 

Dual

Compressor 2

 

 

 

Compressor

 

 

 

5

Freeze sensor lockout

 

 

 

 

(optional item)

 

 

 

 

 

 

 

 

 

 

Condensate overflow

Red

 

6

in coil drain pan

 

 

 

(optional item)

 

 

 

Brownout AC voltage

 

 

7

to R and C terminal

 

 

 

below 18 VAC

 

 

 

 

 

 

1

High pressure lockout

 

 

 

 

 

 

2

Low pressure lockout

 

 

 

 

 

 

3

Freeze sensor lockout

 

 

(optional item)

 

Single

 

 

 

 

 

 

Condensate overflow

 

Compressor

 

 

4

in coil drain pan

 

 

 

 

 

(optional item)

 

 

 

 

 

 

 

Brownout AC voltage

 

 

5

to R and C terminals

 

 

 

below 18 VAC

 

 

 

 

Intelligent Reset

If a fault condition is initiated, the five minute delay on break time period and the random start timer is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. A single condensate overflow fault will cause the unit to go into a hard lockout immediately, and will require a manual lockout reset.

Your UPM board will come from the factory with the following default settings:

Default Settings

Freeze

NO

 

 

Temp

35°

 

 

Lockout

2

 

 

Reset

T

 

 

Alarm

CONT

 

 

Test

NO

 

 

Hot/Dry Alarm

HOT

 

 

Model ERCH-HP Energy Recovery Unit 27