4.5.5.10 Factory Menu

Chapter 4: E2 Controller

 

Table 4-10. Factory default setpoints.

 

 

Parameter

Default Value

 

 

Temperature Setpoint

72° F

 

 

Compressor Cut- in

74° F

 

 

Compressor Cut- out

72.3° F

 

 

Minimum Fan Speed

40%

 

 

Maximum Fan Speed

100%

 

 

Dehumidification Fan Speed

60%

 

 

Humidity Setpoint

45% RH

 

 

Dehumidify Cut-in

50% RH

 

 

Dehumidify Cut-out

47% RH

 

 

Figure 4-63. Set Passwords screen.

The second Service>Save Cfg menu screen allows you to set new passwords for entering the Control and Service menus.

4.5.5.10 Factory Menu

Figure 4-64. Factory Menu screen.

The Factory Menu loop may be accessed from the Service>Factory screen. You must enter the factory-level password to gain access to the loop. Contact Black Box Tech Support for the password and for guidance when adjustments must be made at this level.