Chapter 4: E2 Controller
| Table |
|
|
Parameter | Default Value |
|
|
Temperature Setpoint | 72° F |
|
|
Compressor Cut- in | 74° F |
|
|
Compressor Cut- out | 72.3° F |
|
|
Minimum Fan Speed | 40% |
|
|
Maximum Fan Speed | 100% |
|
|
Dehumidification Fan Speed | 60% |
|
|
Humidity Setpoint | 45% RH |
|
|
Dehumidify | 50% RH |
|
|
Dehumidify | 47% RH |
|
|
Figure
The second Service>Save Cfg menu screen allows you to set new passwords for entering the Control and Service menus.
4.5.5.10 Factory Menu
Figure
The Factory Menu loop may be accessed from the Service>Factory screen. You must enter the