Chapter 4: E2 Controller
Factory>Group>Group Status (Screen 8) provides an overview of the current duty status for all the A/C units combined in the group.
Table
Display Description | Description | Variables | Default |
|
|
|
|
Running | Display indicates how many units in the group are currently operating. | 0 to 8 | 0 |
|
|
|
|
Active | Display indicates how many units in the group are currently active. | 0 to 8 | 0 |
|
|
|
|
Standby | Display indicates how many units in the group are currently in standby. | 0 to 8 | 0 |
|
|
|
|
Assist | Display indicates how many units in the group are currently operating in the capacity assist mode. | 0 to 8 | 0 |
|
|
|
|
Online | Display indicates how many units in the group are currently available to operate. | 0 to 8 | 0 |
|
|
|
|
Out of Service | Display indicates how many units in the group are not available to operate. |
|
|
|
|
|
|
The final step to configure a workgroup is to access the Service>Options>Group Setup screens used to configure parameters that apply to how individual A/C units interact in the workgroup (see Section 4.6.2.7).
Figure
Table
Display Description | Description | Variables | Default | ||
|
|
|
| ||
Lead unit | Display indicates which unit is currently the lead. | 0 to 8 | 0 | ||
|
|
|
|
| |
Plan timer | Display indicates the time delay (in seconds) between the detection of | 0 to 60 | 30 | ||
a communication failure and the annunciation of a Comm alarm. | |||||
|
|
|
| ||
|
|
|
|
| |
pLAN present | Display indicates if a pLAN is detected by the controller. | 0 | = No | No | |
1 | = Yes | ||||
|
|
| |||
|
|
|
|
|
4.6.2.7 Service>Options>Group Menu Screens
Accessed in the Service menu, the Service>Options>Group Setup screens only appear if two or more units are wired together as a workgroup.
Group Setup