Chapter 4: E2 Controller
Table 4-17. Group alarms 1 to 8.
Number | Description | Bitmask | Default |
|
|
|
|
1 | Humidifier | 1 | 0 |
|
|
|
|
2 | Pump | 2 | 0 |
|
|
|
|
3 | Customer alarm 1 | 4 | 0 |
|
|
|
|
4 | Circuit 1 high pressure | 8 | 0 |
|
|
|
|
5 | Circuit 1 low pressure | 16 | 0 |
|
|
|
|
6 | DX lockout | 32 | 0 |
|
|
|
|
7 | Humidifier lockout | 64 | 0 |
|
|
|
|
8 | FC/AWS lockout | 128 | 0 |
|
|
|
|
Table 4-18. Group alarms 9 to 16.
Number | Description | Bitmask | Default |
|
|
|
|
9 | Upper fan alarm | 1 | 0 |
|
|
|
|
10 | Middle fan alarm | 2 | 0 |
|
|
|
|
11 | Lower fan alarm | 4 | 0 |
|
|
|
|
12 | Water detection | 8 | 0 |
|
|
|
|
13 | Condensate pan | 16 | 0 |
|
|
|
|
14 | Moisture | 32 | 0 |
|
|
|
|
15 | Filter | 64 | 0 |
|
|
|
|
16 | Reserved | 128 | 0 |
|
|
|
|
Page 94 |