Black Box CRDX-G-FS-12KW, CRDX-W-FS-12KW 5.1.6 A/C System, Troubleshooting, Maintenance, Page

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 116
Image 116
5.1.6 A/C System

Chapter 5: Maintenance

5.1.6 A/C System

Check the refrigerant sight glass on a monthly basis while the unit is running and ensure it is free of bubbles. Bubbles in the sight glass indicate a low refrigerant charge or a clogged filter-drier. Check for humidity in the refrigerant by viewing the color of the indicator in the center of the sight glass and comparing it to the color scale on the outer ring. If humidity is present, the system must be evacuated and recharged.

Check the superheat and sub-cooling temperatures semi-annually and ensure they are within the range shown in the refrigerant pressure/temperature table (Tables 2-9–2-11) in Section 2.10.3. If necessary, adjust the refrigerant charge to achieve the correct values. If the

refrigerant level is low, check the system for leaks.

5.2 Troubleshooting

Turn off all power to the unit before conducting any troubleshooting procedures, unless the procedure specifically requires the system to operate. For troubleshooting purposes, the system may be operated with the doors open by using a pair of channel lock pliers to turn the shaft of the main power disconnect switch to the “On” position. When the switch is turned on, high voltage will be present inside the cabinet. Exercise caution to prevent injury. Keep hands, clothing, and tools clear of the electrical terminals and rotating components. Ensure that your footing is stable at all times.

Symptom: Airflow too low.

Probable Cause: Dirty air filters (reduced airflow).

Recommendation: Clean/replace filters.

Symptom: EC fan(s) fail to start.

Probable Causes/Recommendations:

a. Power failure. Check main voltage power source input cable.

b. Motor starter protector tripped. Reset motor starter protector and check amperage of motor.

c. Control transformer circuit breaker tripped. Check for short circuit or ground fault; if none, reset circuit breaker.

d. Condensate overflow switch open.

1.Ensure unit is level.

2.Check that condensate pan is draining.

e.Defective contactor. Repair or replace.

f.No control signal to fan(s). Check the control I/O board for a 0-10 VDC control signal to the fan(s). Refer to the electric drawing to determine the correct I/O board terminal numbers. This must done within 15 seconds of turning the disconnect switch “On” or the controller will go into “Air Proving Alarm” mode.

g.EC fan’s internal overheat protection. Determine the cause of the interruption and correct. Possible causes are:

1.Blocked rotor.

2.Low supply voltage > 5 seconds.

3.Loss of phase > 5 seconds.

After causes 1, 2, and 3 are corrected, the motor will automatically reset.

After the causes below are corrected, the fan(s) must be manually reset by turning off power for 20 seconds:

4.Over temperature of electronics.

5.Over temperature of motor.

Page 116

724-746-5500 blackbox.com

Page 116
Image 116
Black Box CRDX-G-FS-12KW, CRDX-W-FS-12KW, CRDX-A-FS-24KW user manual 5.1.6 A/C System, Troubleshooting, Maintenance, Page