Black Box CRDX-W-FS-12KW Settings and Adjustments 2.11.1 Water-Water/Glycol Circuit, EC Fans

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 42
Image 42
2.11Settings and Adjustments 2.11.1 Water–Water/Glycol Circuit

Chapter 2: Installation

2.11Settings and Adjustments 2.11.1 Water–Water/Glycol Circuit

Condensing temperature is maintained by liquid flowing through a regulating valve and then into the condenser. The regulating valve opens to increase the liquid flow as the refrigerant pressure rises (or closes as the refrigerant pressure falls). The system controller monitors a signal from a pressure transducer to determine how far to open the valve. The controller automatically changes the control valve position to maintain head pressure based on the difference between the setpoint value and the actual measured value. The controller transmits a proportional 0– to 10–VDC signal to the regulating valve with 10 VDC corresponding to the valve opening 100%.

The system controller is factory set for the correct condensing pressure; however, it can be adjusted to increase or decrease the pressure. To adjust the pressure, enter the Factory menu in the E2 controller. Contact Black Box Technical Support at

724-746-5500 or info@blackbox.com for a password to enter the Factory menu and for technical assistance if adjustment is necessary.

Make adjustments in small increments. Allow adequate time between adjustments for the valve to fully respond to the control signal so you can observe the changes in system operation.

2.11.2 Low-/High-Pressure Limit Switch

Air-conditioning systems using DX refrigerant are equipped with hermetically sealed high-pressure and low-pressure switches. These switches are pre-set by the manufacturer and cannot be adjusted. The high-pressure switch opens at 630 psig and has a manual reset. The low-pressure switch opens at 65 psig (± 10) and closes at 105 psig (± 10) and has an automatic reset.

2.11.3 Thermal Expansion Valve

An electronically controlled expansion valve (EEV) maintains constant superheat of the refrigerant vapor at the outlet of the evaporator by metering the flow of refrigerant into the evaporator. Superheat is the difference between the refrigerant vapor temperature and its saturation temperature at a given suction pressure. By controlling superheat, the EEV keeps nearly the entire evaporator surface active while preventing liquid refrigerant from returning to the compressor. As a standard, superheat is factory set at 12–15° F and should not need adjustment. The superheat temperature is monitored and controlled by the auxiliary control module (EVD Driver) mounted on the door of the electric box. We recommend that you contact Black Box Technical Support if adjustment is required.

CAUTION 2.11.2 Low-/High-Pressure Limit Switch

Do not exceed 20° F superheat. Exceeding this temperature may cause failure of the compressor.

2.11.4 Hot Gas Bypass

A electronic hot gas bypass system is provided for freeze protection and capacity control. The auxiliary control module (EVD Driver) mounted on the door of the electric box manages operation of the hot gas valve. The hot gas regulator valve allows refrigerant to flow from the discharge line directly to the evaporator through an auxiliary connection downstream of the thermal expansion valve. This is used to maintain the evaporator at a minimum constant pressure as the heating load varies.

The hot gas (discharge) regulating valve is set to prevent the surface temperature of the evaporator coil from dropping below 35° F. The bypass temperature is factory set and no adjustment should be necessary. Contact Black Box Technical Support at 724-746-5500 or info@blackbox.com if adjustment is required.

2.11.5 EC Fans

The speed of the EC fans is controlled via a 0– to 10–VDC signal from the system controller. The controller is preset by the factory for the correct fan speed configuration and should not require adjustment. If the airflow needs to be adjusted, this may be done using the controller’s programming menu selections. Refer to Section 4.4.4 for instructions on adjusting airflow using the system controller. Contact Black Box Technical Support at 724-746-5500 or info@blackbox.com when initially making adjustments to the controller.

Page 42

724-746-5500 blackbox.com

Page 42
Image 42
Black Box CRDX-W-FS-12KW Settings and Adjustments 2.11.1 Water-Water/Glycol Circuit, Low-/High-Pressure Limit Switch, Page