Chapter 5: Maintenance

Symptom: Noisy compressor.

Probable Causes/Recommendations:

a. Expansion valve stuck in open position (abnormally cold suction line). Ensure feeder bulb is tight on suction line. Check operation and superheat.

b. Broken compressor valve (compressor knocking, suction pressure rises faster than 2 lb./min. after shutdown). Replace compressor.

c. Worn or scarred compressor bearings. Replace compressor.

d. Liquid slugging. System overcharged. Reclaim excess refrigerant.

e. Scroll compressor not properly phased. Phase correctly at main power source. DO NOT REWIRE COMPRESSOR.

5.3 Field Service

Repairs must be performed by a journeyman refrigeration mechanic or air-conditioning technician. Turn off power to unit at the main power disconnect switch before attempting to make repairs.

NOTE: Do not attempt to make repairs without the proper tools.

5.3.1 Water–Water/Glycol System

If the water or water/glycol system isn’t cooling or if cooling is reduced, check for fluid leaks in the system. Check for clogged water lines. If filters are installed in the fluid lines, check the condition of the filters. Clean or replace the filters if necessary.

In situations where scaling could be heavy, untreated water in the unit cooling coils may cause, over a period of time, a loss of heat exchange capacity from a mineral deposit build-up inside the coil. Only a qualified service mechanic should clean dirty coils.

Leak Detection/Repair

A leak in a fluid cooling system will usually form a puddle of fluid beneath the unit that can be easily seen. Visually trace the leak up from the puddle to the area on the unit where fluid may be seen dripping.

When a leak is detected, turn off the fluid supply before attempting repairs. Adjacent piping must be thoroughly cleaned by removing all paint, dirt and oily film. Use a wire brush, sandcloth, or sandpaper and wipe the area with clean, dry cloths. Protect nearby parts from heat damage by wrapping with watersoaked cloths.

For copper-to-copper (piping) repairs, use a phosphorus copper brazing alloy with 15% silver. Use general-purpose silver brazing alloy with 45% silver for copper-to-brass or copper-to steel repairs.

When repairs are completed, remove all traces of flux and flush the system. After any repair, pressurize the system to check for leaks before recharging the system.

5.3.2 DX System

You might need to perform repairs on the refrigeration system. If field repairs are necessary, the following procedures apply:

5.3.2.1 Leak Detection

Several methods can be used to detect a leak in the refrigeration system. The most modern and easiest method is to use an electronic leak detector. Follow the manufacturer’s directions to quickly locate any leak. A second method is to use soap bubbles. Apply a solution of soapy water with a brush or sponge to the joints and connections in the refrigeration lines. A leak in the lines will cause bubbles to form.

5.3.2.2 Leak Repair

When a leak is located, properly reclaim the remaining refrigerant charge before beginning repairs. Adjacent piping must be thoroughly cleaned by removing all paint, dirt, and oily film. Use a wire brush, sandcloth, or sandpaper and wipe the area with clean, dry cloths. Protect nearby parts from heat damage by wrapping with water-soaked cloths.

724-746-5500 blackbox.com

Page 119

Page 119
Image 119
Black Box CRDX-W-FS-12KW Field Service, Water-Water/Glycol System, Leak Detection/Repair, DX System, Leak Repair

CRDX-W-FS-12KW, Black Box Cold Row DX, CRDX-W-FS-24KW, CRDX-A-FS-24KW, CRDX-A-FS-12KW specifications

The Black Box CRDX series consists of high-performance cooling solutions designed to maintain optimal temperature conditions in data centers and server rooms. Key models in this series include the CRDX-W-FS-12KW, CRDX-W-FS-24KW, CRDX-G-FS-12KW, and CRDX-A-FS-24KW. These units are engineered to provide efficient cooling while addressing the rising demands of modern IT infrastructure.

One of the standout features of the CRDX series is its cold row design. This configuration enables targeted cooling delivery directly to the equipment, enhancing efficiency and reducing energy consumption. The airflow management in these models ensures that cooled air is directed where it is needed most, minimizing hotspots and maximizing cooling performance.

Both the CRDX-W-FS-12KW and CRDX-W-FS-24KW models utilize advanced refrigerant-based cooling technology. These units are equipped with electronically commutated (EC) fans, which are highly efficient and quieter than traditional fan technologies. This innovation not only lowers operational costs but also creates a more comfortable environment within the data center.

The CRDX-G-FS-12KW model stands out for its hybrid capabilities, offering both chilled water and direct expansion cooling options. This versatility allows facility managers to choose the best cooling approach based on their specific requirements and current infrastructure. The hybrid system can optimize energy consumption and enhance cooling efficiency, contributing to lower operating costs.

Another noteworthy feature across these models is their intelligent controls and monitoring capabilities. Equipped with sophisticated sensors and control systems, operators can gain real-time insights into temperature fluctuations, humidity levels, and unit performance. This data aids in proactive maintenance and ensures that cooling systems are operating at peak efficiency.

The CRDX-A-FS-24KW, on the other hand, is designed with a focus on adaptability and scalability. This model can be integrated easily into existing network setups, making it an excellent choice for facilities that anticipate future growth or need to adapt to changing cooling demands.

Overall, the Black Box CRDX series exemplifies the latest advancements in cooling technology, offering innovative features designed to support high-density computing environments. With their efficient cooling capabilities, intelligent controls, and flexible design options, these models provide reliable solutions for data centers looking to enhance their cooling systems while reducing operating costs.