Black Box CRDX-W-FS-24KW, CRDX-W-FS-12KW Configure the Terminal Address, E2 Controller, Page

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 87
Image 87
4.6.2.1 Configure the Terminal Address

Chapter 4: E2 Controller

A workgroup should ALWAYS start with controller address 1 and go up from there. DO NOT skip over controller addresses. The list of suitable controller/display terminal address pairs is shown below:

Table 4-11. Corresponding Controller to Terminal pLAN Addresses.

Controller (I/O board)

1

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

Display Terminal

32

31

30

29

28

27

26

25

 

 

 

 

 

 

 

 

 

You must assign the terminal and controller I/O board addresses for each controller to be grouped. Review Sections 4.6.2.1 to

4.6.2.3first, before turning power on and assigning addresses. Do not interconnect the controllers together before assigning their terminal and I/O board pLAN addresses.

The first step is to change the terminal address of each controller to 0, referring to Section 4.6.2.1 below. You must set the terminal address to 0 before you can assign the controller (I/O board) address.

NOTE: If the terminal remains inactive (no key is pressed) for more than 30 seconds, the group setup procedure is exited automatically, without saving any changes.

4.6.2.1 Configure the Terminal Address

The address of the terminal (display) can only be configured if its telephone jack is connected to the I/O control module in the electric box and power is turned on. The factory default value for the display terminal address is 32. To reassign the terminal

address, press and hold the (up-arrow ( Manual background), down-arrow ( Manual background) and Enter (Manual background) keys simultaneously for five seconds until the Address Configuration screen shown below appears with the flashing cursor in the top left corner:

Figure 4-68. Terminal (Display) Address screen.

1.To change the address of the terminal (Display address setting), press the Enter Manual background key once. The cursor will move to the address field (nn).

2.Use the up Manual background and down Manual background arrow keys to select the desired value (0), and confirm by pressing Enter Manual background again.

Figure 4-69. Display Address screen.

The Display Address Changed screen will appear, indicating the display address selected is not the same as the one saved previously and the new value will be saved to the permanent memory.

3. Once the terminal address is set to zero, cycle the power to the unit Off and then back On.

NOTE: If the “Display address setting:__" field is set to 0, the terminal will communicate with the controller (I/O board) using point-to-point protocol (not pLAN). The display field “I/O Board address:__” will disappear as it has no meaning until you set the controller (I/O board) pLAN address.

724-746-5500 blackbox.com

Page 87

Page 87
Image 87
Black Box CRDX-W-FS-24KW, CRDX-W-FS-12KW, CRDX-A-FS-24KW, CRDX-G-FS-24KW Configure the Terminal Address, E2 Controller, Page