Black Box CRDX-W-FS-24KW, CRDX-W-FS-12KW, CRDX-A-FS-24KW Setpoint Adjustment, E2 Controller, Page

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 52
Image 52
4.3.1 Setpoint Adjustment

Chapter 4: E2 Controller

NOTE: You may turn the A/C unit on and off at any time by pressing and holding the Enter key for 3 seconds.

Other status messages that may appear at the bottom of the screen are:

“OFF by remote shutdown” indicates the Remote Start/Stop feature is enabled and requires a remote start switch to be turned On.

“OFF by Network” indicates the unit is part of a group and is off because of a grouping priority command such as a compressor alarm or loss of airflow, or the BMS communication feature is enabled and the unit received a network signal to pause operation.

“OFF by Internal Alarm” indicates that the unit is off because of a group alarm condition. (Only active with grouped units.)

“Unit on CL Lockout” indicates cooling has been locked out while there is a demand for dehumidification because the temperature is below the minimum temperature allowable for dehumidification (factory default setting is 4° F below setpoint).

4.After the initialization period expires, the controller enables the control output to the fluid control valve (CRDX-W-FS-12KW, CRDX-W-FS-24KW, CRDX-G-FS-12KW, CRDX-G-FS-24W) and the fans are allowed to begin operating.

5.The Black Box logo in the display is replaced with a blower Manual background symbol. The fans begin operating in stages with five-second time delays. The middle fan starts first, then the upper fan, then the lower fan.

6.Following a 45-second time delay (after the first fan turns on), the controller polls the air proving switch. If adequate airflow is detected, the controller enables the compressor to turn on if there is a demand for cooling or dehumidification as defined by the control setpoints.

Figure 4-13. Controller polls screen.

7.The controller records the date and time power is reinitialized in the alarm history log.

8.If the actual room conditions are not within the range of the programmed setpoints, the system will begin operating in the mode(s) needed to reach the setpoints (cooling or dehumidifying). Symbols appear to indicate the active operating modes.

Manual background = Blower On

Manual background = Call For Cooling

Manual background = Dehumidifying

9.Temperature and humidity alarms are masked out for 30 minutes to allow conditions to stabilize without triggering nuisance alarms.

10.Operator interface to the menu loops is available from the Main screen by pressing the Program (Prg) key. The controller starts a timer whenever a key sequence is initiated. Every time a button is pressed, the timer is reset. If there is no key activity for 60 seconds, the controller will return to the Main screen unless the Screen Lock feature is enabled in the Information menu loop (see Section 4.5.2).

4.3.1 Setpoint Adjustment

1.From the Main screen, access the Main Menu screen by pressing the program Manual background key.

2.Scroll through the Main Menu selections with the Up Manual background and Down Manual background arrow keys and select the Control menu by pressing the Enter Manual background key when “CONTROL” appears in bold letters in the center of the screen. A password entry screen will be displayed.

3.To access the Control menu, press the Enter Manual background key twice to insert a flashing cursor in the “Enter Password” field.

Page 52

724-746-5500 blackbox.com

Page 52
Image 52
Black Box CRDX-W-FS-24KW, CRDX-W-FS-12KW, CRDX-A-FS-24KW, CRDX-G-FS-24KW user manual Setpoint Adjustment, E2 Controller, Page