Black Box CRDX-W-FS-24KW user manual E2 Controller, Page, 7. Alarms 25 to 32 Sensor failure alarms

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 80
Image 80
Table 4-7. Alarms 25 to 32 (Sensor failure alarms).

Chapter 4: E2 Controller

Table 4-7. Alarms 25 to 32 (Sensor failure alarms).

Number

Description

Bitmask

Default

 

 

 

 

25

Lower temperature sensor fail

1

1

 

 

 

 

26

Middle temperature sensor fail

2

2

 

 

 

 

27

Optional temperature sensor fail

4

4

 

 

 

 

28

Upper temperature sensor fail

8

8

 

 

 

 

29

Return humidity sensor fail

16

16

 

 

 

 

30

DX1 discharge pressure fail

32

32

 

 

 

 

31

Static air pressure sensor fail

64

64

 

 

 

 

32

DX1 suction press sensor fail

128

128

 

 

 

Factory Default Bitmask Total

 

255

 

 

 

 

Table 4-8. Alarms 33 to 40 (Sensor failure alarms).

Number

Description

Bitmask

Default

 

 

 

 

33

DX1 suction temp sensor fail

1

1

 

 

 

 

34

Custom sensor 1 fail

2

2

 

 

 

 

35

Reserved

4

0

 

 

 

 

36

Reserved

8

0

 

 

 

 

37

Reserved

16

0

 

 

 

 

38

Reserved

32

0

 

 

 

 

39

Reserved

64

0

 

 

 

 

40

Reserved

128

0

 

 

 

Factory Default Bitmask Total

 

3

 

 

 

 

Page 80

724-746-5500 blackbox.com

Page 80
Image 80
Black Box CRDX-W-FS-24KW, CRDX-W-FS-12KW, CRDX-A-FS-24KW E2 Controller, Page, 7. Alarms 25 to 32 Sensor failure alarms