Chapter 4: E2 Controller
Table 4-21. Group alarms 33 to 40.
Number | Description | Bitmask | Default |
|
|
|
|
33 | Static air pressure | 1 | 0 |
|
|
|
|
34 | Differential air pressure | 2 | 0 |
|
|
|
|
35 | Dewpoint | 4 | 0 |
|
|
|
|
36 | Airspeed | 8 | 0 |
|
|
|
|
37 | Reserved | 16 | 0 |
|
|
|
|
38 | Reserved | 32 | 0 |
|
|
|
|
39 | Reserved | 64 | 0 |
|
|
|
|
40 | Reserved | 128 | 0 |
|
|
|
|
There are several automatic crossover signals that will cause a switchover from Unit Active to Unit Off. They are the occurrence of a remote shutdown command, unit shutdown from a group alarm or BMS command, fire/smoke detection, loss of all cooling (all compressors or all CW valves), or loss of airflow.
Figure
The Factory>Group Screen 7, provides an overview of pLAN workgroup.
Table
Display Description | Description | Variables | Default | |
|
|
|
| |
Group Status | Indicates if multiple A/C unit grouping is enabled. | 0= On | 0 | |
1= Off | ||||
|
|
| ||
|
|
|
| |
C 1 2 3 4 5 6 7 8 | Indicates the address |
| 1 | |
|
|
|
| |
| Indicates the address |
| 32 | |
T 5 6 7 8 9 0 1 2 | pLAN. The terminal address numbers range from 25 to 32 but only the |
|
last digit appears in the screen.
Figure
Page 96 |