Chapter 1: Introduction
1.5.1 Electrical Compartment
The electrical components are protected inside an electric box located behind the rear access panel. The electric box cover is safety interlocked with the service disconnect switch (See Figure
The service disconnect switch may be used to turn the unit off for emergency shutdown or when routine maintenance is performed. The handle of the switch locks in the “Off” position to prevent unintended operation.
1.5.2 Circuit Breakers/Motor Start Protectors
Cold Row units incorporate
1.5.3 Compressor
A scroll compressor is used in
1.5.3.1 Electronic Thermal Expansion Valve
An auxiliary control module mounted to the door of the electric box manages the operation of the electronic expansion valve (EEV). The control module manages the EEV based on input signals from the suction pressure and temperature sensors. It regulates the amount of refrigerant entering the evaporator to maintain the correct superheat temperature.
1.5.3.2 Electronic Hot Gas Bypass
Used for freeze protection and capacity control, an electronically controlled hot gas bypass valve is managed by the same auxiliary control module that manages the EEV valve. The hot gas bypass system allows the compressor to run continuously instead of cycling the compressor on and off for capacity control. The hot gas bypass system manages system capacity based on the suction temperature. The hot gas regulator valve meters hot gas into the evaporator coil during low load periods or when evaporator airflow is reduced.
1.5.4 Coils
Cooling coils are constructed of aluminum finned/copper tube. The coils are leak tested and cleaned before installation by the factory. Condensate drain pans are provided to collect water condensed by the coils. A condensate pump empties the drain pans and directs the water to a pipe stub located either at the top or the bottom of the A/C unit depending on the piping configuration (see Section 2.7.1 and 2.8.1.1).
A float switch in the lower condensate pan detects if the water level rises. If the condensate pan fails to drain, the float switch signals the controller to sound an alarm and turn off the compressor and the fans.
1.5.5 Condensate Pump
A condensate pump is factory installed in the lower drain pan. The pump automatically eliminates condensate water from the drain pan. The pump has an internal float switch that turns the pump on and off based on the water level.
1.5.6 EC Fans
The unit is equipped with three
The fans do not use drive belts. Fan speed is variable via a 0- to
Page 17 |