Black Box CRDX-G-FS-24KW, CRDX-W-FS-12KW Variable/Value Descriptions, E2 Controller, Page

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 107
Image 107
Variable/Value Descriptions

Chapter 4: E2 Controller

Variable/Value Descriptions

Table 4-30. Variable/Value Descriptions.

Variable

Description for

Description for

Description for

Description for

Description for

Description for

Description for

Description

Value 0

Value 1

Value 2

Value 3

Value 4

Value 5

Value 6

 

 

 

 

 

 

 

 

Fan link control

None

Upper & middle

Upper & lower

Middle & lower

All

 

 

 

 

 

 

 

 

[X] fan speed

Manual

Temperature

Variance from

control

proportionate

average

 

 

 

 

 

 

 

 

 

 

 

 

 

Type of unit

Not selected

CW-12"

CW-24"

AR-12"

AR-24"

W/G-12"

W/G-24"

 

 

 

 

 

 

 

 

4.9.3 Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet

Table 4-31. Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet.

BMS

Modbus

BACnet

 

 

 

Address

Address

Address

Description

Default

Direction

 

 

 

 

 

 

1

002

1

Global alarm output

0

R

 

 

 

 

 

 

r

003

2

System on status

0

R

 

 

 

 

 

 

3

004

3

Airflow has been proven

0

R

 

 

 

 

 

 

4

005

4

Call for cooling

0

R

 

 

 

 

 

 

5

006

5

Call for humidification

0

R

 

 

 

 

 

 

6

007

6

Call for dehumidification

0

R

 

 

 

 

 

 

100

101

100

BMS value to pause the unit

0

R/W

 

 

 

 

 

 

101

102

101

BMS value to reset alarms

0

R/W

 

 

 

 

 

 

102

103

102

Force rotation of units in group manual or BMS

0

R/W

 

 

 

 

 

 

103

104

103

BMS value to switch CW sources

0

R/W

 

 

 

 

 

 

104

105

104

BMS value to switch dual power primary

0

R/W

 

 

 

 

 

 

105

106

105

BMS value to activate lockout function

0

R/W

 

 

 

 

 

 

106

107

106

Reset dirty filter alarm

0

R/W

 

 

 

 

 

 