2.10.3.2 Saturated Refrigerant Pressure

Chapter 2: Installation

2.10.3Refrigerant Characteristics 2.10.3.1 Pressure/Temperature Settings

The following table is provided to assist with the normal settings of the system for R410A refrigerant. Where applicable, minimum and maximum settings are given along with normal operating pressures.

Table 2-11. R410A refrigerant pressure/temperature settings.

 

Normal

Min.

Max.

 

 

 

 

Sub-cooling °F

10

5

20

 

 

 

 

Superheat °F

15

10

20

 

 

 

 

Design Condensing Temp. @ 95°F

125

105

140

Ambient

 

 

 

 

 

 

 

Suction Pressure (psig)

130

105

140

 

 

 

 

Fan Cycling Control—Fan On (psig)

440

330

480

 

 

 

 

Fan Speed Control (psig)

440

 

 

 

 

2.10.3.2 Saturated Refrigerant Pressure

The following refrigerant temperature/pressure table is provided for reference for R410A refrigerant.

Table 2-12. R410A refrigerant pressures.

Temperature (°F)

Pressure (psig)

Temperature (°F)

Pressure (psig)

 

 

 

 

20

78.4

75

218

 

 

 

 

22

81.9

80

236

 

 

 

 

24

85.5

85

255

 

 

 

 

26

89.2

90

274

 

 

 

 

28

93.1

95

295

 

 

 

 

30

97.0

100

318

 

 

 

 

32

101

105

341

 

 

 

 

34

105

110

365

 

 

 

 

36

109

115

391

 

 

 

 

38

114

120

418

 

 

 

 

40

118

125

446

 

 

 

 

42

123

130

477

 

 

 

 

44

128

135

508

 

 

 

 

46

133

140

541

 

 

 

 

48

137

 

 

 

 

50

143

 

 

 

 

55

155

 

 

 

 

60

170

 

 

 

 

65

185

 

 

 

 

70

201

 

 

 

 