Chapter 4: E2 Controller

4.4.3.2 Water–W/G Operation

When the system is turned on, the controller activates the fluid supply control valve with a proportional/integral (P/I), 0–10 VDC signal. The valve opens proportionally based on head pressure. The control parameters are adjustable in the Factory menu. If adjustment is required, contact Black Box Technical Support at 724-746-5500 or info@blackbox.com.

The control valve changes position to adjust coolant flow to keep the head pressure to the control setpoint and maintain it. If the head pressure rises, the valve position continues to modulate open as needed, up to 100% (fully open), to maintain the control setpoint.

The control output signal is matched to the valve. If the valve typically opens at 2.5 VDC, the control I/O module will generate the appropriate voltage for opening the valve starting at the minimum voltage of 2.5 VDC. From there the signal increases as needed until the valve position reaches 100% open.

4.4.3.3 Dehumidifying

When dehumidification is called for, the blower speed automatically changes to the dehumidification fan speed setting. The controller will operate the system in the cooling mode at full output to strip moisture from the air. The system will remain in the cooling mode until the actual relative humidity (or dewpoint) reaches the control setpoint plus the dehumidification cut-out offset. If the control temperature drops below the low temperature cutout setpoint for the dehumidification mode (temperature setpoint minus 4° F default), cooling operations will stop.

4.4.4 Airflow/Fan Speed Control

The E2 controller treats each EC fan as a variable speed fan. The controller manages the speed of each fan from a factory-set minimum up to a factory-set maximum speed. The minimum fan speed is used whenever the A/C unit has no cooling operations running. The maximum fan speed setting is used during times when the A/C unit is cooling. A dehumidification fan speed setting is used when the system is in the dehumidification mode. The speed settings are adjustable in the Service>Blower>Blower Set Up menu loop (see Section 4.5.5.4).

EC fan speed is automatically varied based on temperature. There are mechanisms to trade off the control valve opening versus fan speed. When the system enters the dehumidification mode, the fan speed automatically changes to the dehumidification speed setting.

The E2 controller's software is equipped with an operational fail-safe mode. Upon sensing a temperature sensor failure, the controller signals an alarm. It continues to develop the fan control outputs by calculating the averaged value of the remaining sensors to replace the input value of the failed sensor. If all the temperature sensors fail, the controller develops the control outputs based on the entered temperature setpoint value minus a 3° F temperature offset. This allows the Cold Row system to continue operating while the cause of the problem is corrected.

The controller continually monitors fan operation. Cold Row DX units are equipped with a pneumatic air proving system connect- ed to a flow switch that detects the loss of airflow when a fan fails to operate.

If one of the fans fails to operate, the controller alerts the operator with an alarm message and increases the speed of the remaining two fans to 99.9% to compensate for the loss of airflow. If the fault does not clear, the fans shut down for 5 seconds and then restart. If the fault continues, the fans reset a second time. If the fault does not clear after the second reset, the fan(s) that generated the fault are shut down and the remaining fans continue operation at 99.9% speed.

If the BMS monitoring/control signal fails, the E2 controller will default to local operation at the current setpoints for the fans. The local sensors have priority over the BMS system.

Page 58

724-746-5500 blackbox.com

Page 58
Image 58
Black Box CRDX-G-FS-24KW, CRDX-W-FS-12KW, CRDX-A-FS-24KW Water-W/G Operation, Dehumidifying, Airflow/Fan Speed Control

CRDX-W-FS-12KW, Black Box Cold Row DX, CRDX-W-FS-24KW, CRDX-A-FS-24KW, CRDX-A-FS-12KW specifications

The Black Box CRDX series consists of high-performance cooling solutions designed to maintain optimal temperature conditions in data centers and server rooms. Key models in this series include the CRDX-W-FS-12KW, CRDX-W-FS-24KW, CRDX-G-FS-12KW, and CRDX-A-FS-24KW. These units are engineered to provide efficient cooling while addressing the rising demands of modern IT infrastructure.

One of the standout features of the CRDX series is its cold row design. This configuration enables targeted cooling delivery directly to the equipment, enhancing efficiency and reducing energy consumption. The airflow management in these models ensures that cooled air is directed where it is needed most, minimizing hotspots and maximizing cooling performance.

Both the CRDX-W-FS-12KW and CRDX-W-FS-24KW models utilize advanced refrigerant-based cooling technology. These units are equipped with electronically commutated (EC) fans, which are highly efficient and quieter than traditional fan technologies. This innovation not only lowers operational costs but also creates a more comfortable environment within the data center.

The CRDX-G-FS-12KW model stands out for its hybrid capabilities, offering both chilled water and direct expansion cooling options. This versatility allows facility managers to choose the best cooling approach based on their specific requirements and current infrastructure. The hybrid system can optimize energy consumption and enhance cooling efficiency, contributing to lower operating costs.

Another noteworthy feature across these models is their intelligent controls and monitoring capabilities. Equipped with sophisticated sensors and control systems, operators can gain real-time insights into temperature fluctuations, humidity levels, and unit performance. This data aids in proactive maintenance and ensures that cooling systems are operating at peak efficiency.

The CRDX-A-FS-24KW, on the other hand, is designed with a focus on adaptability and scalability. This model can be integrated easily into existing network setups, making it an excellent choice for facilities that anticipate future growth or need to adapt to changing cooling demands.

Overall, the Black Box CRDX series exemplifies the latest advancements in cooling technology, offering innovative features designed to support high-density computing environments. With their efficient cooling capabilities, intelligent controls, and flexible design options, these models provide reliable solutions for data centers looking to enhance their cooling systems while reducing operating costs.