Black Box CRDX-W-FS-12KW, CRDX-A-FS-24KW, CRDX-G-FS-24KW, CRDX-W-FS-24KW E2 Controller, Page

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 112
Image 112
4.9.8 Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet

Chapter 4: E2 Controller

4.9.8 Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet

Table 4-36. Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.

BMS

Modbus

BACnet

 

 

 

Address

Address

Address

Description

Default

Direction

 

 

 

 

 

 

100

229

1100

BMS keep alive parameter

0

R/W

 

 

 

 

 

 

101

230

1101

BMS low fan speed for CW units

0

R/W

 

 

 

 

 

 

102

231

1102

BMS run fan speed for CW units

0

R/W

 

 

 

 

 

 

103

232

1103

BMS dehum fan speed for CW units

0

R/W

 

 

 

 

 

 

4.9.9 Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet

Table 4-37. Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet.

BMS

Modbus

BACnet

 

 

 

Address

Address

Address

Description

Default

Direction

 

 

 

 

 

 

100

101

1100

BMS value to pause the unit

0

R/W

 

 

 

 

 

 

101

102

1101

BMS value to reset alarms

0

R/W

 

 

 

 

 

 

102

103

1102

Force rotation of units in group manual or BMS 0

0

R/W

 

 

 

 

 

 

103

104

1103

BMS value to switch CW sources

0

R/W

 

 

 

 

 

 

104

105

1104

BMS value to switch dual power primary

0

R/W

 

 

 

 

 

 

Page 112

724-746-5500 blackbox.com

Page 112
Image 112