Chapter 4: E2 Controller

4.9.1 Signed Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet

Table 4-28. Signed Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.

BMS

Modbus

BACnet

 

 

 

Address

Address

Address

Description

Default

Read/Write

 

 

 

 

 

 

1

002

1

Temperature setpoint

72.0

R/W

 

 

 

 

 

 

2

003

2

Humidity setpoint

45.0

R/Ws

 

 

 

 

 

 

3

004

3

Average supply temperature display value

0.0

R

 

 

 

 

 

 

4

005

4

Return humidity sensor current value

0.0

R

 

 

 

 

 

 

5

006

5

Dewpoint of return temperature and humidity

0.0

R

 

 

 

 

 

 

6

007

6

Dewpoint of remote temperature and humidity

0.0

R

 

 

 

 

 

 

7

008

7

Middle fan speed

0.0

R

 

 

 

 

 

 

8

009

8

Upper fan speed

0.0

R

 

 

 

 

 

 

9

010

9

Lower fan speed

0.0

R

 

 

 

 

 

 

10

011

10

Middle fan manual speed

0.0

R/W

 

 

 

 

 

 

11

012

11

Upper fan manual speed

0.0

R/W

 

 

 

 

 

 

12

013

12

Lower fan manual speed

0.0

R/W

 

 

 

 

 

 

13

014

13

Static pressure sensor current value

0.0

R

 

 

 

 

 

 

14

015

14

C1 discharge pressure sensor current value

0.0

R

 

 

 

 

 

 

15

016

15

C1 suction pressure sensor current value

0.0

R

 

 

 

 

 

 

16

017

16

C1 suction temperature sensor current value

0.0

R

 

 

 

 

 

 

17

018

17

Return temperature display value

0.0

R

 

 

 

 

 

 

18

019

18

Remote temperature display value

0.0

R

 

 

 

 

 

 

19

020

19

Entering water temperature display value

0.0

R

 

 

 

 

 

 

20

021

20

Leaving water temperature display value

0.0

R

 

 

 

 

 

 

100

101

100

High air temperature alarm limit

80.0

R/W

 

 

 

 

 

 

101

102

101

Low temperature alarm limit

60.0

R/W

 

 

 

 

 

 

102

103

102

High humidity alarm limit

70.0

R/W

 

 

 

 

 

 

103

104

103

Low humidity alarm limit

30.0

R/W

 

 

 

 

 

 

104

105

104

High water temperature limit

60.0

R/W

 

 

 

 

 

 

105

106

105

Low water temperature alarm limit

40.0

R/W

 

 

 

 

 

 