Black Box CRDX-W-FS-12KW E2 Controller, Page, 76. FactoryGroupsGroups Config Screen 1. See Table

Models: CRDX-W-FS-12KW Black Box Cold Row DX CRDX-W-FS-24KW CRDX-A-FS-24KW CRDX-A-FS-12KW CRDX-G-FS-12KW CRDX-G-FS-24KW

1 132
Download 132 pages 49.93 Kb
Page 91
Image 91
Figure 4-76. Factory>Groups>Groups Config (Screen 1). (See Table 4-12.)

Chapter 4: E2 Controller

Figure 4-76. Factory>Groups>Groups Config (Screen 1). (See Table 4-12.)

Table 4-12. Factory>Groups>Groups Config (Screen 1) parameters.

Display

 

 

 

Description

Description

Variables

Default

 

 

 

 

 

 

0= Out of Service

 

 

 

1= Active

 

 

Assign the duty of the A/C unit within the group.

2= Standby

 

Unit

The duty must be assigned for each A/C unit at its local display terminal.

3= Assist

1

 

 

4= Active_No_Rot

 

 

 

5= Standby_No_Rot

 

 

 

6= Assist_No_Rot

 

 

 

 

 

Total in Network

Enter the total number of A/C units in the group.

0 to 9

1

 

 

 

 

Min Number Active

Enter the total number of active A/C units in the group.

0 to 9

1

 

 

 

 

Enb lead override

If set to yes, you may manually assign the lead unit in the following field.

0= No

No

1= Yes

 

 

 

 

 

 

 

Lead Unit

Lead Unit Identifies which A/C unit controller is currently the lead unit in the group.

1 to 8

1

If "Enb lead override" is set to yes, you may select which unit is lead.

 

 

 

 

 

 

 

Figure 4-77. Factory>Group>Group Rotation (Screen 2).

From this screen, you may set the schedule to rotate operation of the A/C units to promote equal run times.

724-746-5500 blackbox.com