Chapter 2: Installation
Figure
2.10 System Charging Procedures
2.10.1 Water–Water/Glycol Cooled Systems
No field refrigerant charging is required for
•The piping system must be cleaned prior to allowing water or water/glycol to flow through the system.
•Glycol must be mixed with water before it is added to the system. Use only water/glycol solution with inhibitors for corrosion protection.
•When filling the
1.Open a vent valve at highest point of the system.
2.Fill the system until the solution is discharging from the vent with minimal signs of foaming caused by air in the system.
2.10.2 Remote Air-Cooled Systems
Remote
NOTE: Refrigerant charging must be performed by a qualified
Cold Row systems use R410A refrigerant. R410A is a blended refrigerant recognized for being safe for the environment. Refrigerants that are multicomponent blends have component parts with different volatilities that result in a change in composition and saturation temperature as evaporation and condensation occur. The composition of liquid R410A refrigerant, however, remains relatively constant.
Page 36 |