Chapter 4: E2 Controller
Figure
Group Sensor Values
This displays the current group temperature and humidity control values transmitted from the Lead controller. The field below displays the selected control T/H sensor arrangement (lead, avg, min, max, local) depending upon how the group is set up. See Service>Options screens, Section 4.6.2.7. The last field shows the unit group address assigned to the controller within the group and the address of the current lead controller.
Group Alarms
This screen only appears when the controller is wired with additional A/C unit controllers. It displays bitmask values indicating the alarm conditions that will initiate a group internal alarm causing the unit to switch over from “Active" to "Unit Off.” See Factory>Group (Group Alarm Setup) in Section 4.6.2.6.
Lead Controller Group Sensors
This screen appears only in the display of the controller that is designated as the lead in a
Group Sensor Status
This screen appears only in the display of the controller that is designated as the Lead in a
1 = Supply Temperature Sensor
2 = Return Humidity Sensor
4 = Remote Supply Temperature Sensor
8 = Remote Supply Humidity Sensor
16 = Static Pressure Sensor
To determine which sensors are enabled and operable for each unit, simply determine which index numbers, derived from the key above, will produce the number shown in the screen.
In the example shown, the number for the lead unit is 15. This results from adding 1 Supply Temperature + 2 Return Humidity + 4 Remote Supply Temperature + 8 Remote Supply Humidity together, confirming those sensors are operable.