Chapter 4: E2 Controller

4.9.2 Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet

Table 4-29. Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.

BMS

Modbus

BACnet

 

 

 

Address

Address

Address

Description

Default

Read/Write

1

130

1001

Cooling analog output

0

R

 

 

 

 

 

 

2

131

1002

Middle fan Speed analog output

0

R

 

 

 

 

 

 

3

132

1003

Upper fan analog control value

0

R

 

 

 

 

 

 

4

133

1004

Lower Fan analog control value

0

R

 

 

 

 

 

 

5

134

1005

Packed bit for BMS - alarms

0

R

 

 

 

 

 

 

6

135

1006

Packed bit for BMS - alarms

0

R

 

 

 

 

 

 

7

136

1007

Packed bit for BMS - alarms

0

R

 

 

 

 

 

 

8

137

1008

Packed bit for BMS - sensor fails

0

R

 

 

 

 

 

 

9

138

1009

Packed bit for BMS - sensor fails

0

R

 

 

 

 

 

 

10

139

1010

Packed bit for BMS - digital inputs

0

R

 

 

 

 

 

 

11

140

1011

Packed bit for BMS - digital inputs

0

R

 

 

 

 

 

 

12

141

1012

Packed bit for BMS - digital outputs

0

R

 

 

 

 

 

 

13

142

1013

Packed bit for BMS - digital outputs

0

R

 

 

 

 

 

 

15

144

1015

Prop humidifier control output

0

R

 

 

 

 

 

 

16

145

1016

Head pressure control output

0

R

 

 

 

 

 

 

100

229

1100

BMS keep alive parameter

0

R/W

 

 

 

 

 

 

101

230

1101

BMS low fan speed for CW units

0

R/W

 

 

 

 

 

 

102

231

1102

BMS run fan speed for CW units

0

R/W

 

 

 

 

 

 

103

232

1103

BMS dehumidifier fan speed for CW units

0

R/W

 

 

 

 

 

 

104

233

1104

Fan link control (0 to 4) See 4.9.2.1

0

R/W

 

 

 

 

 

 

105

234

1105

Control mode of dewpoint, hybrid, standard

0

R/W

 

 

 

 

 

 

106

235

1106

Temperature control sensor selection

0

R/W

 

 

 

 

 

 

107

236

1107

Humidity control sensor selection

0

R/W

 

 

 

 

 

 

108

237

1108

Type of unit (valid numbers 0 to 6) See 4.9.2.1

0

R/W

 

 

 

 

 

 

110

239

1110

Lower fan speed control (0 to 2) See 4.9.2.1

0

R/W

 

 

 

 

 

 

111

240

1111

Middle fan speed control (0 to 2) See 4.9.2.1

0

R/W

 

 

 

 

 

 

112

241

1112

Upper fan speed control (0 to 2) See 4.9.2.1

0

R/W

 

 

 

 

 

 

123

252

1123

Current day

0

R/W

 

 

 

 

 

 

124

253

1124

Current month

1

R/W

 

 

 

 

 

 

125

254

1125

Current year

1

R/W

 

 

 

 

 

 

126

255

1126

Current hour

0

R/W

 

 

 

 

 

 

127

256

1127

Current minute

0

R/W

 

 

 

 

 

 

Page 106

724-746-5500 blackbox.com

Page 106
Image 106
Black Box CRDX-A-FS-24KW, CRDX-W-FS-12KW, CRDX-G-FS-24KW, CRDX-W-FS-24KW user manual Type of unit valid numbers 0 to 6 See

CRDX-W-FS-12KW, Black Box Cold Row DX, CRDX-W-FS-24KW, CRDX-A-FS-24KW, CRDX-A-FS-12KW specifications

The Black Box CRDX series consists of high-performance cooling solutions designed to maintain optimal temperature conditions in data centers and server rooms. Key models in this series include the CRDX-W-FS-12KW, CRDX-W-FS-24KW, CRDX-G-FS-12KW, and CRDX-A-FS-24KW. These units are engineered to provide efficient cooling while addressing the rising demands of modern IT infrastructure.

One of the standout features of the CRDX series is its cold row design. This configuration enables targeted cooling delivery directly to the equipment, enhancing efficiency and reducing energy consumption. The airflow management in these models ensures that cooled air is directed where it is needed most, minimizing hotspots and maximizing cooling performance.

Both the CRDX-W-FS-12KW and CRDX-W-FS-24KW models utilize advanced refrigerant-based cooling technology. These units are equipped with electronically commutated (EC) fans, which are highly efficient and quieter than traditional fan technologies. This innovation not only lowers operational costs but also creates a more comfortable environment within the data center.

The CRDX-G-FS-12KW model stands out for its hybrid capabilities, offering both chilled water and direct expansion cooling options. This versatility allows facility managers to choose the best cooling approach based on their specific requirements and current infrastructure. The hybrid system can optimize energy consumption and enhance cooling efficiency, contributing to lower operating costs.

Another noteworthy feature across these models is their intelligent controls and monitoring capabilities. Equipped with sophisticated sensors and control systems, operators can gain real-time insights into temperature fluctuations, humidity levels, and unit performance. This data aids in proactive maintenance and ensures that cooling systems are operating at peak efficiency.

The CRDX-A-FS-24KW, on the other hand, is designed with a focus on adaptability and scalability. This model can be integrated easily into existing network setups, making it an excellent choice for facilities that anticipate future growth or need to adapt to changing cooling demands.

Overall, the Black Box CRDX series exemplifies the latest advancements in cooling technology, offering innovative features designed to support high-density computing environments. With their efficient cooling capabilities, intelligent controls, and flexible design options, these models provide reliable solutions for data centers looking to enhance their cooling systems while reducing operating costs.