4.9.6 Digital Input Packed Bit Variables

Chapter 4: E2 Controller

4.9.6 Digital Input Packed Bit Variables

Table 4-34. Digital Input Packed Bit Variables.

Bit

Digital Inputs 1

Digital Inputs 2

 

 

 

0

Remote shutdown

Customer alarm 2

 

 

 

1

Customer alarm 1

Customer alarm 3

 

 

 

2

Water

Reserved

 

 

 

3

Condensate pan

Reserved

 

 

 

4

Humidifier

Reserved

 

 

 

5

Moisture

Reserved

 

 

 

6

Middle fan alarm

Reserved

 

 

 

7

Upper fan alarm

Reserved

 

 

 

8

Fire/smoke

Reserved

 

 

 

9

Lower fan alarm

Reserved

 

 

 

10

Dual power input A

Reserved

 

 

 

11

Dual power input B

Reserved

 

 

 

12

Circuit 1 low pressure

Reserved

 

 

 

13

Circuit 1 high pressure

Reserved

 

 

 

14

Pump alarm

Reserved

 

 

 

15

Humidifier lockout

Reserved

 

 

 