![Energy Wheel Troubleshooting](/images/new-backgrounds/32451/3245147x1.webp)
Energy Wheel Troubleshooting
Symptom | Possible Cause | Corrective Action | |
|
|
| |
| Air seals are too tight. | See air seals under | |
| section. | ||
Energy wheel |
| ||
|
| ||
Broken belt. | Replace. | ||
does NOT turn | |||
|
| ||
No power to wheel motor. | Make sure wheel drive is plugged in. Verify | ||
| |||
| power is available. | ||
|
| ||
|
|
| |
Energy wheel | Wheel motor overloads are tripping due to | Recheck air seals, make sure they are not too | |
tight. See Adjust the Air Seals under | |||
runs intermittently | rubbing between wheel and air seals. | Energy Wheel section. | |
|
| ||
|
|
|
Heat Pump Overview
Every unit has a complete, sealed refrigeration system that is ready for connection to a water source.
The heat pump has all the typical DX components and also has refrigerant reversing valve(s) to enable the system to work in both heating and cooling modes.
Factory-Installed Heat Pump System Components:
Thermostatic Expansion Valve (TXV)
Each compressor is equipped with a thermal expansion valve. The valve controls the flow of liquid refrigerant entering the evaporator coil by maintaining a constant, factory set superheat of 10ºF.
Refrigerant Distributor
Attached to the TXV is a refrigerant distributor. The refrigerant distributor evenly distributes the refrigerant to each circuit of the airside coil to provide optimum performance.
Airside Coil
Each unit uses a single refrigerant coil known as an airside coil. If two compressors are used in the unit, then the airside coil will be a split configuration so that each compressor has a dedicated portion of the airside coil. Depending on whether the unit is in cooling or heating mode, the airside coil will function as either
a condensing coil or an evaporator coil. See also Subassemblies/Coils.
Coaxial
Liquid Line Filter Drier
The liquid line filter drier prevents moisture and foreign matter from entering the thermal expansion valve. It is located in the compressor compartment.
Hot Gas Bypass Valve
On units equipped with hot bypass, hot gas from the compressor is injected into the liquid line of the airside coil after the TXV. This process starts when suction gas temperatures drop below 28ºF, which is
Valve Adjustment: To adjust the valve, connect a pressure gauge to the suction line and block the entering air to the coil. The valve should begin to open when the suction pressure drops to approximately 58 PSIG (the valve will feel warm to the touch). Adjustments are made by first removing the cap
on the valve and then turning the adjusting stem counterclockwise to decrease the pressure. Allow several minutes between adjustments for system to stabilize. When adjustment is complete, replace the cap on the valve.
Reversing Valve
Each compressor is equipped with a reversing valve to reverse the direction of refrigerant flow. The valve is electrically actuated.
Access Ports
For easy measurement and charging access, several ports are provided throughout the system. These can be used to measure system pressures and also charge or evacuate the system.
24Model