Greenheck Fan 473501 manual Electrical Controls, Optional Frost Control, Testing, Timer

Models: 473501

1 40
Download 40 pages 12.86 Kb
Page 19
Image 19
Electrical Controls

Electrical Controls

Optional Frost Control

Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the enthalpy wheel. Frost control is an optional feature that will prevent/control wheel frosting. Three options are available:

1.Timed Exhaust frost control

2.Electric preheat frost control

3.Modulating wheel frost control

All of these options are provided with a thermostat (with probe) mounted in the outdoor air intake compartment and a pressure sensor to monitor pressure drop across the enthalpy wheel. The typical temperature setting corresponds to the indoor air relative humidity as

shown in the

 

 

Frost Threshold Temperatures

Frost Threshold

 

 

Temperatures

Indoor RH

Frost Threshold

table and

at 70°F

Temperature

represents when

20%

-10º F

frost can occur.

 

 

30%

-5º F

An increase in

 

 

40%

0º F

pressure drop

 

 

 

 

would indicate that frost is occurring. Both the pressure sensor and the outdoor air temperature sensor must trigger in order to initiate frost control. The two sensors together ensure that frost control is only initiated during a real frost condition. Field wiring of a light (or other alarm) between 6 and C in the control center will notify personnel when unit is in frost control mode.The following explains the three options in more detail.

Timed exhaust frost control includes a timer in addition to the thermostat and wheel pressure sensor. When timed exhaust frost control is initiated, the timer will turn the supply blower on and off to allow the warm exhaust air to defrost the enthalpy wheel. Default factory settings are 5 minutes off and 30 minutes on. Use the following test procedure for troubleshooting.

Testing (refer to Timer diagram)

Turn the temperature sensor up as high as possible. The supply blower should cycle on for one minute, then turn off for one minute.

After testing, set the Timer Scale as follows: T1 = 10 minutes, T2 = 1 hour

Set the Timer Settings as follows:

T1 = 0.5, T2 = 0.5. The timer is now set for 5 minutes off and 30 minutes on. Remember to remove the jumper.

Electric preheat frost control includes an electric heater (at outdoor air intake) and an airflow pressure switch (located at the preheater) in addition to the thermostat and pressure sensor on wheel. When electric preheat frost control is initiated, the electric preheater will turn on and warm the air entering the energy wheel to avoid frosting. Use the following test procedure for troubleshooting.

Testing

If no DDC controller is present, jumper thermodisc and jumper the wheel pressure sensor. The heater should turn on.

If it doesn’t, either put the outdoor airside doors on or temporarily jumper the airflow pressure switch in the preheater control center to avoid nuisance tripping of the pressure switch. Also check the airflow switch pressure tap located at the supply discharge blower to ensure the tubing is connected and the tap is not blocked. Remember to remove the jumpers.

Modulating wheel frost control includes a variable frequency drive in addition to the thermostat and pressure sensor. When modulating wheel frost control is initiated, the variable frequency drive will reduce the speed of the wheel. Reducing the speed of the energy wheel reduces its effectiveness, which keeps the exhaust air condition from reaching saturation, thus, eliminating condensation and frosting. If the outdoor air temperature is greater than the frost threshold

Jumper the wheel pressure switch in the unit control center. Set the Timer Scale for T1 and T2 to 1 minute. Set the Timer Settings for T1 and T2 to 1.0. Set the dip switch to the down position. (normal position)

A1 B1 15

0.8

0.6

1.0

0.4

0

0.2

T2

1 MIN T2

 

Timer

Scale

1 MIN T1

0.8 0.6

Optional Frost Control 1.0 0.4 0 0.2

T1

Dip Switch

temperature OR the pressure differential is less than the set point, the wheel will run at full speed. If the outdoor air temperature is less than the frost threshold temperature AND the pressure differential is greater than the set point, the wheel will run at reduced speed until the pressure differential falls below the set point. The temperature and pressure differential set points are set at the factory, but are field-adjustable. The variable frequency drive will be fully programmed at the factory.

16 18 A2

Timer

Model ERCH-HP Energy Recovery Unit 19

Page 19
Image 19
Greenheck Fan 473501 manual Electrical Controls, Optional Frost Control, Testing, Timer