Use of Solvent Cement and Primer

Venting instructions

 

10. Insert the vent piping through this hole and secure into

1. Plan the venting layout starting at the vent termination

 

 

 

position. Connect the vent pipe to the end termination

 

and work back toward the heater. Take into considera-

 

 

 

elbow as shown in Figures.9-11.

 

 

 

 

 

 

 

 

 

 

 

 

 

tion the style and position of the vent termination, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vent pipe routing, elbows and connectors required and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the necessary support hangers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. G/JW 40, 50 and 60-gallon heaters may use 50mm (2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in.) or 76mm (3 in.) venting depending on "Equivalent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Length" as described in Table 2. G/JW5065 high

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEALANT

 

input models require 76mm (3 in.) venting. See also the

 

 

ATTACH 90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

section on "Vent pipe connection to blower".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Venting should be as direct as possible with the fewest

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELBOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT PIPING MAY BE

 

number of fittings. Use long radius 45 degree and long

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RODENT SCREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLOPED IN

 

ANY

 

radius 90 degree elbows wherever possible.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIRECTION, AS LONG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Do not use 90 degree elbows "back to back" (other than

 

 

 

 

 

 

(INSTALL INTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AS A WATER TRAP IS

 

 

 

 

 

 

 

 

ELBOW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT

 

CREATED IN

 

termination installations) and do not use street elbows.

 

 

300mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THE VENTING SYS-

 

Maintain a minimum 150mm (6 in.) straight section

 

 

(12 in.)

 

 

GROUND LEVEL

SEALANT

 

 

 

 

 

 

 

 

 

TEM.

 

THE

SLOPE

 

 

 

MIN.

 

 

OR MAXIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHOULD BE KEPT TO

 

between elbows. Closely coupled and short radius

 

 

 

 

 

 

SNOW LINE*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A MINIMUM

SO AS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

elbows reduce the venting capacity (see Figure 6 and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT TO EXERT ANY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNDUE STRESS ON

 

the note below it).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THE PIPE.

 

 

 

5.

DO NOT USE AN ELBOW AS A SUPPORT POINT.

 

 

* WHERE SNOW COVER IS NORMAL DURING WINTER, ENSURE

 

 

 

 

Elbows are not designed to carry the weight of the vent-

 

 

 

 

 

 

 

 

SUFFICIENT VENT CLEARANCE TO PREVENT BLOCKAGE OR ICE BUILDUP.

 

ing system.

 

 

Figure 9 Vent Termination Exterior Installation

 

 

 

6. Calculate "Equivalent Vent Length" before starting. Do

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not exceed the values shown in Table 2. An example of

 

 

ATTACH 90°

 

BRACKET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

how this length is determined is shown in Figure 8. The

 

 

TERMINATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELBOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value from your calculations should also be used to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

determine which rodent screen to install into the vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

termination elbow.

 

 

 

 

 

RODENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EQUIVALENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7. Measure the vent piping and cut to required lengths.

 

 

 

 

 

SCREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT LENGTH

 

 

 

 

 

 

(INSTALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MEASURED FROM

 

 

Pipes must be cut at right angles and deburred to

 

 

 

 

 

INTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THIS POSITION

 

 

ensure a good smooth fit with sufficient overlap for the

 

 

 

 

 

ELBOW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEALANT

 

 

 

 

 

 

 

300mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

glue joints. Correct any interference conditions.

 

 

(12 in.)

 

 

 

VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8. Provide support hangers for horizontal vent piping every

 

 

MIN.

 

 

 

RISER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2m (4 ft.) to prevent sagging and stress. Provide a

 

 

 

GROUND LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT PIPING TO BE

 

minimum of 3mm (1/8 in.) rise per 1.2m (4 ft.) of vent

 

 

 

OR MAXIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SNOW LINE*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLOPED (DOWN)

 

piping to ensure adequate drainage. Horizontal vent

 

 

 

 

 

 

 

 

 

SEALANT

 

 

 

 

 

 

 

 

 

 

 

 

TOWARD HEATER TO

 

piping must not sag to form valleys where condensate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREVENT WATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FROM COLLECTING.

 

may collect. Vertical venting shall be supported every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5m (5 ft.). Use appropriate support straps and vibra-

 

 

* WHERE SNOW COVER IS NORMAL DURING WINTER, ENSURE

 

 

 

 

tion isolators (foam pads) on straight sections only. Do

 

 

SUFFICIENT VENT CLEARANCE TO PREVENT BLOCKAGE OR ICE BUILDUP.

 

not use elbows as support points. Allow sufficient clear-

 

 

Figure 10 Installation Of Fabricated Vent Riser.

 

 

 

 

ance for expansion and contraction of the venting sys-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tem.

 

 

 

 

 

 

 

76mm (3 in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MIN. LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

9. At the point where the vent pipe exits the building, cut a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAY BE 90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELBOW

 

65mm (2-1/2 in.) hole for 50mm (2 in.) venting or a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90mm (3-1/2 in.) hole for 76mm (3 in.) venting.

 

 

A VENT USED IN A SPECIAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RODENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTING SYSTEM

WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450mm

 

 

 

 

 

 

 

 

 

Use of Solvent Cement and Primer

 

 

POSITIVE VENT PRESSURE

 

 

 

 

 

 

 

 

(18 in.)

 

 

 

 

 

(INSTALL

 

 

 

• Use only in well-ventilated areas.

 

 

AND PASSING THROUGH A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEAST

450mm

(18 in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOF SHALL EXTEND AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELBOW)

 

 

 

• Do not use near flame or open fire.

 

 

ABOVE

THE

HIGHEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use only the Solvent Cement and Primer

 

 

POINT WHERE IT PASSES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOF

 

 

THROUGH THE ROOF SUR-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

appropriate for the venting material being

 

 

FACE

AND ANY

OTHER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OBSTRUCTION

WITHIN A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

used.

 

 

HORIZONTAL DISTANCE OF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Solvent cements for plastic pipe are flam-

 

 

450mm (18 in.). A VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTING SYSTEM

MUST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mable liquids and must be kept away from

 

 

BE SUPPORTED

EVERY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5m (5 ft.).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

all sources of ignition.

 

Figure 11 Vertical Venting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 13
Image 13
GSW 319594-000 Use of Solvent Cement and Primer, Use only in well-ventilatedareas, Do not use near flame or open fire