SYMPTOM | POSSIBLE CAUSE(S) |
| CORRECTIVE ACTION | |
|
|
|
| |
Error 7 | The | 1. | Cycle power to the water heater “OFF” for 10 seconds and then | |
a problem with the gas valve |
| back “ON”. | ||
| driver circuit. | 2. | If the above step did not clear the error, the control must be | |
|
|
|
| replaced. |
|
|
|
| |
Error 8 | The | 1. | Cycle the external power “OFF” for 10 seconds and then back “ON”. | |
detected a problem with the | 2. | If the above step does not clear the error, the control must be | ||
| internal microcomputer. |
| replaced. | |
|
|
|
| |
Error 9 | The | 1. | Cycle the external power “OFF” for 10 seconds and then back “ON”. | |
detected a problem with the | 2. | If the above step does not clear the error, the control must be | ||
| internal circuit. |
| replaced. | |
|
|
|
| |
Error 10 | Flame signal sensed out of | 1. | Insure flame sensor ceramic insulator is not cracked. | |
proper sequence. | 2. | Turn power off for | ||
|
|
|
| error code. |
|
|
| 3. | Replace the control. |
|
|
|
| |
Error 11 | The high temperature thermal | 1. | Turn the power off for | |
cutoff is open. |
| error code. | ||
|
|
| 2. | Replace the control. |
|
|
|
| |
Error 12 | The | 1. | Make sure that there are no objects leaning against the front of the | |
detected one of the tempera- |
| control. | ||
| ture adjust buttons stuck | 2. | Lightly press and release each of the buttons once. | |
| closed. | 3. | If the above actions do not clear the error, the control will continue | |
|
|
|
| to regulate water temperature at the last setting, but you will not be |
|
|
|
| able to change settings unless you replace the control. |
|
|
|
| |
Error 13 | The | 1. | Turn the power off for | |
detected that the water tem- |
| error code. | ||
| perature sensor is either open | 2. | If no wiring problems are found the control must be replaced. | |
| or short circuited. |
|
| |
|
|
|
| |
Error 14 | The | 1. | Check that all wiring is correct and that there are no open or short | |
a problem with the Flammable |
| circuits. | ||
| Vapour Wiring. |
|
| |
|
|
| ||
Error 15 | The control detected the pres- | 1. Check for and remove any sources of flammable vapours. | ||
ence | of flammable vapours | 2. | Check the resistance of the FV sensor. If the resistance is more | |
| near | the appliance and |
| than 100K ohms replace the sensor. |
| entered lockout. | 3. | If the water heater is in operating condition replace the control. | |
|
|
|
|
|
Table 5 (cont’d)