Haier AC18CS1ERA B. Under Ceiling Type, Drilling for piping, anchor bolts, Installation Procedure

Models: AC12CS1ERA AC24CS1ERA AC18CS1ERA

1 102
Download 102 pages 21.54 Kb
Page 15
Image 15
B. UNDER CEILING TYPE

Installation Procedure

Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit. (Fig.7)

Fig.7

OK

NO

NO

Arrange the drain hose

Drain hose

lower than this portion.

 

1.Drilling for piping CAUTION:

Do not install the unit drain hose side is too high. Height A should be less than 5 mm.(Fig.8)

B. UNDER CEILING TYPE

Using the installation template, drill holes for piping and anchor bolts(for holes).(Fig.9)

Fig.8

 

Drain hose

A

A

Fig.9

 

900m

 

 

 

Drilling position

200m

Installation

for anchor bolt

 

template

Ceilling

 

 

 

 

 

Wall

 

Drilling position

 

 

for piping

 

1.Drilling for piping

Select piping and drain directions. (Fig.10)

anchor bolts CAUTION:

Install the drain hose at the rear. It should not be installed on the top or right side.

Fig. 10

Rear (Install the drain

 

 

hose in the direction.)

 

Right

When the directions are selected, drill 80mm and 50mm

Fig.11

or 150mm dia. hole on the wall so that the hole is tilted

 

downward toward the outdoor for smooth water flow.

 

(Fig.11)

 

 

 

2.Drilling holes for anchor bolts and installing the

 

Fig.12

anchor bolts

 

 

With a concrete drill, drill four 12.7 mm dia. Holes.

 

 

(Fig.12)

 

 

Insert the anchor bolts into the drilled holes, and drive

 

Fig.13

 

 

the pins completely into the anchor bolts with a hammer.

 

 

 

(Fig.13)

 

 

 

 

 

Wall

6mm

60 to 70mm

12.7mm

13

Page 15
Image 15
Haier AC18CS1ERA, AC24CS1ERA, AC12CS1ERA B. Under Ceiling Type, Drilling for piping, anchor bolts, Installation Procedure