INSTALLATION MANUAL FOR OUTDOOR UNIT
(6)Additional charge of refrigerant
Outdoor unit is precharged at a factory for the piping length up to 5m. Additional charge is not required up to 5m.
|
| Item | Basic | Factory charge amount | Additional | Length that | Maximum | |
|
| refrigerant | of refrigerant | charge | additional | |||
|
|
| piping | |||||
Model |
| charge |
|
| amount (ii) | charge is not | length | |
| Outdoor unit | Indoor unit | ||||||
|
|
| amount (i) | per meter | required |
| ||
Heat |
| 3.44 | 3.52 | 0 | 0.06 | 5m (viii)(v) | 50m | |
|
|
|
|
|
|
|
| |
pump |
| 2.32 | 2.40 | 0 | 0.06 | 5m (viii)(vii) | 30m | |
|
| |||||||
|
|
|
|
|
|
|
|
Notes (i) Basic refrigerant charge amount means refrigerant amount when refrigerant piping length is 5m.
(ii)When the refrigerant piping length exceeds the length that additional refrigerant charge is not required, charge additional refrigerant based on to the calculated amount of refrigerant per unit piping length.
Example of additional charge amount calculation
Calculate the additional charge amount when the piping length is 25 m. (25 - 5 ) x 0.06 = 1.2
Additional charge amount (kg)
Additional charge amount per 1m (kg/m)
Length that additional refrigerant charge is not required (m)
Total length of the piping (one way) (m)
Additional charge amount of refrigerant =0.70kg(Calculate the amount in any case.)
If air perge with the refrigerant is forbidden at the local, please use the vacuum method (Please see the below figure)
To use vacuum pump
1
Detach the service port's cap of
2
Open the handle at low in gaugemanifold, operate
vacuum pump. If the
Gaugemanifold
Vacuum pump
Gaugemanifold
Vacuum pump
3
Vacuumize for over 15min. And check the level gauge which should read
close the handle 'Lo' in gaugemanifold and stop the 3 Close operation of the vacuum pump.
Check the condition of the scale and hold it for
24