11. Refrigerant pipe

Manual background INSTALLATION MANUAL FOR INDOOR UNIT

11. Refrigerant pipe

[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.]

Manual background The outdoor unit has been charged with refrigerant.

Manual background When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown, use spanner and torque spanner together.

Manual background When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4 rings, then fasten with spanner.

Manual background Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)

Manual background Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown. Manual background Only use seal cushion to bind the joint part of air pipe and heat insulation parts.

Paste the refrigerant oil here

Torque spanner

Manual background Spanner

Pipe joint

Cone nut

Middle size seal cushion (accessory)

(Use seal cushion to bind the pipe joint)

Clamp

Manual background Heat insulation (accessory)

(for liquid pipe)

Manual backgroundManual backgroundManual background Heat insulation (accessory) Gas pipe (for gas pipe)

Liquid pipe

80

510

 

 

 

Liquid pipe

Gas pipe

Electric box

 

 

 

 

 

 

 

Upper

 

 

Air inlet

 

 

310

Air outlet

 

 

 

 

Drain hose connection mouth

530

Down side

30

 

 

 

 

 

VP25 PVC pipe

 

 

 

 

Specification of pipe

Tighten torque

Cone dimension

 

Cone

(mm)

 

A (mm)

 

 

9.52

3270~3990 N.cm

45

 

2

(333~407 kgf.cm)

12.0~12.4

 

R0.4~0.8

 

 

 

90

0.5

 

 

 

15.88

9720~11860 N.cm

 

 

A

22.9~23.3

 

 

(990~1210 kgf.cm)

 

 

 

 

 

 

35

Page 36
Image 36
Haier HDU-24H03/H, HDU-42H03/H, HDU-28H03/H instruction manual Refrigerant pipe, Installation Manual For Indoor Unit

FAQ

What is the importance of heat insulation for the refrigerant pipe?

Heat insulation is crucial to prevent water leakage. Without proper insulation, the pipe can cause water leakage.

What should be used to bind the joint part of the air pipe and heat insulation parts?

Only seal cushion should be used to bind the joint part of the air pipe and heat insulation parts.

How can I check if the connection pipe is leaking?

After connecting the pipe, check for any leaks. If there are leaks, perform heat insulation treatment as shown in the figure.