INSTALLATION MANUAL FOR OUTDOOR UNIT
4
Open the valve rod for the
the inspection of gas leakage.
|
|
|
| ||
| Open |
|
|
| |
| Service port |
| Open | Service port | |
90 | 90 4 90 for 6 sec. | 90 | |||
90 | 4 90 for 6 sec. |
5 | In case of gas leakage, tighten |
No gas leakage? | parts of pipe connection. If |
| leakage stops, then proceed 6 |
6 | steps. |
|
Detach the charge hose from the service port, open
7
To prevent the gas leakage, turn the service port's cap, the valve rod'd cap for
8
After attaching the each caps, check the gas leakage around the caps.
If it does not stop gas leakage, discharge whole refrigerants from the serice port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.
Liquid pipe 9.52mm | ||
| ||
6 | Gas pipe 19.05mm | |
6 | 6 | |
6 | ||
| ||
| ||
| ||
| 7 Valve rod cap | |
7 | Valve rod cap |
7 Service port cap
CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.
7 Valve rod cap
5. Electric wiring
7 Service port cap 7 Valve rod cap
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1)Selection of size of power supply and interconnecting wires. Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
Item |
| Circuit | breaker | Power source | Earth leakage breaker | ||
|
|
|
|
| |||
Model | Phase | Switch breaker | Overcurrent protector | wire size | Switch | Leak | |
| (A) | rated capacity (A) | (minimum) | breaker | current | ||
3 | 30 | 20 | 2.5mm2 | 30 | 30mA | ||
1 | 40 | 26 | 4.0mm2 | 40 | 30mA | ||
|
|
|
|
|
| ||
|
|
| 25 |
|
|
|