6. Test run

Manual background INSTALLATION MANUAL FOR OUTDOOR UNIT

(2)Wiring connection

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by *and*terminals.

Outdoor unit

TB1

R

S

T

N

Circuit breaker

 

 

 

 

 

 

 

 

Earth leakage

Indoor

Outdoor

breaker

unit

unit

 

 

 

 

 

 

 

TB1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit breaker

 

Earth leakage

Indoor

breaker

unit

TB2 HIGH VOLTAGE

1

2

3

2

Interconnecting wires

TB

1

2

3

HDU-42H03/H

TB2 HIGH VOLTAGE

1

2

3

1Interconnecting

Manual background wires

TB

1

2

3

HDU-24H03/H HDU-28H03/H

Manual backgroundManual backgroundWARNING

DO NOT CONNECT THE NEUTRAL WIRE N TO R , S OR T PHASE. INTERCONNECT- ING WIRES MUST BE WIRED WITH SAME SYMBOLS ON THE TERMINALS OF BOTH INDOOR AND OUTDOOR UNIT.INCORRECT WIRING CAUSE EQUIPMENT DAMAGE OR

AFIRE.

(3)Wiring procedure

1)Remove set screws on the side before taking off the front panel toward the direction shown in figure.

2)Connect wires to the terminal block correctly and fix the wires with a wire clamp equipped near by the terminal block.

3)Route the wires in a proper way and penetrate the wires through the opening for electric wiring on the side panel.

6. Test run

Front panel

Opening for electric wiring

Manual backgroundManual backgroundCAUTION

THIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION WHEN ELECTRIC POWER IS SUPPLIED.

BE SURE TO EXECUTE "OFF" OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING.

This unit has a function of automatic restart system after recovering power stoppage.

(1)Before starting test run (for all Heat pump models)

Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hrs to energize the crankcase heater in advance of operation.

(2)Test run

Run the unit continuously for about 30 minutes, and check the following.

Suction pressure at check joint of service valve for gas pipe.

Discharge pressure at check joint on the compressor discharge pipe.

Temperature difference between return air and supply air for indoor unit.

26

Page 27
Image 27
Haier HDU-24H03/H, HDU-42H03/H, HDU-28H03/H instruction manual Test run, Installation Manual For Outdoor Unit

FAQ

What is the wiring procedure outlined in the manual?

The manual provides a step-by-step wiring procedure, including removing set screws, connecting wires to the terminal block, and routing the wires properly.

How long should the test run be for Heat pump models?

The manual recommends running the unit continuously for about 30 minutes during the test run.

Does the unit have an automatic restart system after power stoppage?

Yes, the unit has a function of automatic restart system after recovering power stoppage, as stated in the manual.