INSTALLATION MANUAL FOR INDOOR UNIT

10. The operation method of fan controller

Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted.

It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment). The air volume set should be in the operation air volume range.

Figure I shows the position of fan controller in the electric box and operation method.

After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No. accordant. And confirm if it reaches the needed air volume.

Note:

1)When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply.

2)Do not set the dial at the position less than 1.

3)The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity number may exceed the permitted operation capacity range, so it is impossible to operate.

4)When delivering from factory, the capacity number of fan controller is set at ìNo.5î.

Rotate this switch

(capacity number setting:

No. 1 ~ No. 8)

Once the fan controller has trouble, this linker can perform emergency assistant control. When this linker is connected to the linker from the PCB, it can operate with total load.

When this linker is connected to the linker from the PCB, through the fan speed adjustment panel to adjust speed.

Figure 1

 

 

 

 

High

 

Condition of standard air volume

 

 

 

 

Low

(air volume 100Pa)

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

Example of

 

 

 

 

 

 

 

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

duct

Pa

150

 

 

 

 

 

 

 

*

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

100

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

30

34 35

 

 

 

40

43

 

Lower limit

 

 

 

 

 

 

 

Upper limit

 

 

 

 

 

 

Standard air volume(m3/min)

 

 

Figure 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The example of the method of choosing capacity number:

1)If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 2.

2)If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 4.

34

Page 35
Image 35
Haier HDU-28H03/H, HDU-24H03/H Operation method of fan controller, Example of the method of choosing capacity number

HDU-28H03/H, HDU-42H03/H, HDU-24H03/H specifications

Haier has established itself as a leading name in the HVAC sector, and their HDU series, including models HDU-28H03/H, HDU-42H03/H, and HDU-24H03/H, exemplifies the brand's commitment to quality and efficiency. These air conditioning units are ideal for both residential and commercial use, designed to provide optimal comfort without compromising on energy efficiency.

One of the standout features of the HDU series is its advanced inverter technology. This allows the units to adjust their cooling and heating output based on the current demand, ensuring that energy is used efficiently. As a result, users can expect reduced energy bills while enjoying a consistently comfortable indoor climate. The inverter system minimizes temperature fluctuations by maintaining a steady output, enhancing overall comfort.

Another notable aspect of the HDU models is their high energy efficiency ratings, often reaching levels that exceed industry standards. This is largely due to the use of R32 refrigerant, which has a lower global warming potential compared to traditional refrigerants. The incorporation of R32 not only makes these units more environmentally friendly but also helps to improve efficiency, providing effective cooling and heating performance even in extreme weather conditions.

Additionally, the HDU units boast a wide operating temperature range. They are designed to work seamlessly in a variety of climates, maintaining performance in temperatures as low as -15°C for heating and up to 50°C for cooling. This adaptability makes them a versatile choice for different geographic locations.

Quiet operation is another impressive feature of the HDU series. The indoor units are engineered to operate at whisper-quiet levels, making them ideal for bedrooms, offices, or any space where noise could be a concern. This allows users to enjoy a peaceful environment while maintaining their comfort.

The user-friendly interface and smart features of the HDU models further enhance their appeal. Equipped with modern remote controls and optional Wi-Fi connectivity, users can easily manage their air conditioning settings from anywhere, providing convenience and flexibility.

In summary, the Haier HDU-28H03/H, HDU-42H03/H, and HDU-24H03/H models combine advanced inverter technology, high energy efficiency, a wide operating temperature range, and quiet operation to deliver outstanding performance. Their smart features and eco-friendly refrigerant make them a reliable choice for those seeking comfort and efficiency in their HVAC systems.