5. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes.
NOTE: Model
To install firestops for horizontal runs that pass through either interior or exterior walls:
•Cut a
NOTE: The center of the hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.
•Position the firestops on both sides of the hole previ- ously cut and secure the firestops with nails or screws.
•The heat shields of the firestops MUST BE placed to- wards the top of the hole.
•Continue the vent run through the firestops.
NOTE: There must be NO INSULATION or other combustibles inside the framed firestop opening.
10" |
INTERIOR |
WALL SHIELD |
12" |
Figure 23. 10" x 12" Hole and Vent Pipe |
HEAT SHIELD
TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT
EXTERIOR
FIRESTOP
INTERIOR
FIRESTOP
For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes.
To install firestops for vertical runs that pass through ceilings:
•Position a plumb bob directly over the center of the verti- cal vent component.
•Mark the ceiling to establish the centerpoint of the vent.
•Drill a hole or drive a nail through this centerpoint.
•Check the floor above for any obstructions, such as wir- ing or plumbing runs.
•Reposition the fireplace and vent system, if necessary, to accommodate the ceiling joists and/or obstructions.
•Cut an
•Frame the hole with framing lumber the same size as the ceiling joists.
10" (254mm) | 10" (254mm) | |
| ||
| CHIMNEY | |
| HOLE | |
NEW | EXISTING CEILING | |
JOISTS | ||
FRAMING | ||
| ||
MEMBERS |
| |
CEILING |
| |
Figure 25. 10" x 10" Hole & New Framing Members |
If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole.
Figure 24. Heat Shield, Interior & Exterior Firestops