Hearth and Home Technologies SAPPH-D-CWL Termination Locations, Fire Risk, Explosion Risk

Models: SAPPH-D-CSB SAPPH-D-CWL 839-1460 839-1440 839-1390

1 56
Download 56 pages 20.13 Kb
Page 8
Image 8
Termination Locations

Termination Locations

 

 

 

A.4Vent Termination Minimum Clearances

 

 

 

 

 

20 in. (508mm)

 

WARNING

 

(minimum) to

 

 

Perpendicular

 

Fire Risk.

 

Wall (Gas Only)

 

 

 

 

Explosion Risk.

 

 

HORIZONTAL

Maintain vent clearance to combustibles

 

 

OVERHANG

 

 

 

as specified.

2 FT.

 

 

• Do not pack air space with insulation or other

20 IN.

 

MIN.

VERTICAL

 

materials.

 

LOWEST

WALL

 

 

Failure to keep insulation or other materials

 

DISCHARGE

 

 

OPENING

 

away from vent pipe may cause fire.

TERMINATION

 

 

CAP

 

 

 

 

 

 

 

 

X

 

 

 

12

Measure vertical clearances from this surface.

 

 

ROOF PITCH

 

 

 

IS X/12

 

 

H (MIN.) - MINIMUM HEIGHT FROM ROOF

 

 

TO LOWEST DISCHARGE OPENING

 

 

 

 

Roof Pitch

H (Min.) Ft.

 

 

 

 

Flat to 6/12 ......................................................... 1.0*

 

 

 

 

Over 6/12 to ........................................................7/12

1.25*

 

 

 

 

Over 7/12 to 8/12 ............................................... 1.5*

 

 

 

 

Over 8/12 to 9/12 ............................................... 2.0*

 

 

 

 

Over 9/12 to 10/12 ............................................. 2.5*

 

Measure horizontal clearances from this surface.

Over 10/12 to 11/12 ........................................... 3.25

 

(See Figure 4.4 for specific clearances.)

Over 11/12 to 12/12 ........................................... 4.0

 

Over 12/12 to 14/12 ........................................... 5.0

 

 

 

 

Figure 4.1 Termination Clearances

 

Over 14/12 to 16/12 ........................................... 6.0

 

Over 16/12 to 18/12 ........................................... 7.0

 

 

 

 

 

 

 

 

Over 18/12 to 20/12 ........................................... 7.5

 

Gas or Wood

 

Over 20/12 to 21/12 ........................................... 8.0

 

 

* 3 foot minimum in snow regions

 

 

Termination

 

 

 

20 in. (508mm)

 

 

 

 

 

 

Figure 4.3 Minimum Height from Roof to Lowest Discharge

 

 

 

(minimum) to

 

Gas

 

Perpendicular

Opening

 

 

 

18 in. Termination

Wall (Gas Only)

Figure 4.3 specifies minimum vent heights for various

 

(457mm)

 

 

 

 

A

 

pitched roofs.

 

 

 

 

 

 

 

 

 

Gas Termination

Wood & Fuel Oil Termination

 

 

 

A

6 in. (152mm)

 

20 in. (508mm)

 

 

 

Figure 4.2 Multiple Vertical Termination

 

 

 

Page 8

 

 

Quadra-Fire · Sapphire · 250-7233H

September 1, 2008

Page 8
Image 8
Hearth and Home Technologies SAPPH-D-CWL Termination Locations, A.4Vent Termination Minimum Clearances, Fire Risk, Opening