Hearth and Home Technologies BIR50 Installing Firestop Spacers, Attic Insulation Shield

Models: BIR50

1 36
Download 36 pages 43.43 Kb
Page 14
Image 14

North Star

EPA Certified Fireplace

5. Installing Firestop Spacers

Mark and cut out an opening in the ceiling for the firestop spacer being utilized (14-1/2” x 14-1/2” for an FS338, 14-1/2”

x18-3/8” for an FS339 and 14-1/2” x 23” for an FS340). Frame the opening with the same dimension lumber used in the ceiling joists.

Install the firestop spacer.

These firestop spacers are designed to provide the minimum 2” air space required around the chimney. In all situations, the firestop spacers are to be nailed to the ceiling joists from the bottom or fireplace side, EXCEPT when the space above is an insulated ceiling or attic space. In this situation, the firestop spacer must be nailed from the top side to prevent loose insulation from falling into the required 2” air space around the chimney. See Figure 14A.

CAUTION:

Firestop spacers must be used whenever the chimney penetrates a ceiling/floor area.

6. Attic Insulation Shield

An insulation shield should be installed when there is a possibility of insulation coming into contact with the factory built chimney system. The insulation shield is installed by positioning it over the vertical chimney section where it penetrates a firestop spacer. The firestop spacer will support the insulation shield. See Figure 14B.

7. Double-checking the Chimney Assembly

Continue assembling the chimney sections up through the firestop spacers as needed. While doing so, be aware of the height and unsupported chimney length limitations that are given on page 10 under “Chimney Requirements”.

Check each section by pulling up slightly from the top to ensure proper engagement before installing the succeeding sections. If they have been connected correctly, they will not disengage when tested.

NOTE: Wiring for blowers must be done before framed enclosure is completed. If using a Heat Zone kit, it also must be installed before enclosure is complete.

ROOM ABOVE

ATTIC ABOVE

Figure 14A

Installing the Firestop Spacer

AS8 ATTIC

14-1/2" INSULATION SHIELD

INSULATION

FS338

24"FIRESTOP SPACER

CHIMNEY

10-1/2"

Figure 14B

Installing an Attic Insulation Shield

480-1081

14

4-03

Page 14
Image 14
Hearth and Home Technologies BIR50 Installing Firestop Spacers, Attic Insulation Shield, Installing the Firestop Spacer