Construct a chase of desired materials main- taining a minimum 2” air space around the chimney.

3.Termination Cap

a.Install the chimney sections up through the chase enclosure. When using a TR344 round termination cap, the uppermost top section of pipe must extend 6” above the top of the chase collar to allow installation of the storm collar and termination cap. See Figure 20B.

b.For installations utilizing a TR342 telescop- ing round termination cap, the uppermost chimney section must be below the top of the chase top, but not more than 14-1/2” below the top of the chase top flashing collar. See Figure 20C.

c.For installations utilizing an ST375 square termination cap the last chimney section must not be more than 4-1/2” below the chase top. See Figure 20D.

d.For installation utilizing a TS345/TS345P Square Termination Cap, the uppermost chimney section must not be more than 3” below the chase top. See Figure 20E.

e.Attach the chase top (CT35) to the top of the chase.

f.Install the termination cap, following the instructions provided with it.

Storm Collar

Chase Flashing

2" min

6" min

2" min

Figure 20B - Installing a

TR344 Round Termination

Cap

 

 

 

 

Chase

2" min from

Top of pipe

 

 

chase top to

 

 

flashing

 

 

 

 

top of chase

 

 

 

 

 

Cap

 

 

 

 

flashing

 

 

 

 

 

 

 

 

 

 

standoff

 

 

 

4-1/2"

 

 

 

 

 

 

 

 

 

 

 

max

 

 

 

 

 

 

Figure 20D - Installing an

ST375 Square Termination

Cap

Storm Collar

Chase Flashing

2" min

14-1/2" max

Top of uppermost

chimney section

Figure 20C - Installing a

TR342 Round Telescoping

Termination Cap

Top of pipe

2" min from chase top to

 

top of chase flashing

Chase

3" max

flashing

Figure 20E - Installing

a TS345/TS345P Square

Termination Cap

ROUND TERMINATION CAP

(TR342/TR344)

METAL CHASE TOP

FIRESTOP

SPACER

FALSE

CEILING

WARNING!

Never install a single wall slip section or smoke- pipe in a chase structure. The higher temperature of this single wall pipe may radiate sufficient heat to combustible chase materials to cause a fire.

WARNING!

Detailed instructions for installation of the chase top, storm collar and termination cap are packaged with these parts. To avoid danger of fire, all instructions must be strictly followed, including the provision of air space clearance between chimney system and enclosure.To protect against the effects of corrosion on those parts exposed to the weather, we recommend that the chase top be painted with a rust-resistant paint.

Figure 20A - Chase Assembly

480-1081

20

4-03

Page 20
Image 20