10 Shrouds
A. Shroud Requirements
WARNING! Risk of Fire! Shrouds must be constructed as specified. Improper construction may overheat chase top.
•Chase top shrouds may be field constructed where permitted by regional building codes.
NOTICE: Some regional codes require an
•Hearth & Home Technologies Inc. supplies UL listed shrouds. See your dealer for details.
Shrouds can either be
•DuraChimney II must maintain at least 2 in. (51 mm) clearance from combustible materials.
•The chase enclosure must be ventilated.
•The chase top flashing or
-Material must be 24 ga (.024 in) galvanized steel or equivalent.
-Chase pan must have opening 3 in. (76 mm) larger than outside diameter of chimney pipe with at least a 1/2 in. (13 mm) upturned flange/collar.
-Chase pan must overhang chase by 1/2 in. (13 mm) per side for proper air flow.
-Chase pan must have a 1 in. (25 mm) down turned outside edge (weather prtection).
Allow a 1 in. (25 mm) air gap between storm collar and chase top flashing
1/2 in. (13 mm) air space established by spacers
1/2 in. overhang
Chimney Cap
Storm Collar
Chase Top
Flashing or
Chase Pan
20 in. diameter opening
|
| DuraChimney II |
|
| Pipe |
14 in. (345 mm) |
| 1/2 in. |
| (13 mm) | |
diameter chimney |
| |
|
| |
must extend at least |
|
|
6 in. (152 mm) above | Maintain 2 in. (51 mm) |
|
chase top flashing. |
| |
| clearance between | |
| DuraChimney II and | spacers for chase |
| chase enclosure | top flashing |
Figure 10.1 Shroud Requirements |
|
|
32 | Heat & Glo • |