Hearth and Home Technologies RUTHERFORD-50 owner manual 18 1/2 in. 470 mm, G. Sidewalls/Surrounds

Models: RUTHERFORD-50

1 52
Download 52 pages 33.52 Kb
Page 44
Image 44
G. Sidewalls/Surrounds

G. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 24 in. (305 mm) from the fireplace opening.

Combustible mantel legs, surrounds and stub walls may be constructed per Figure 12.15.

Note: Grid depicts 1 inch squares.

4 in. [102 mm]

 

19 3/4 in. [500 mm]

 

BRICK

FRONT

39°

angle

24 in.

[610mm]

 

 

 

60-7/8 in.

50 in.

FLUSH

FRONT

angle

50°

 

22 3/8 in. [568 mm]

 

 

 

18 1/2 in. [470 mm]

24 in. [610mm]

 

 

 

 

 

 

 

 

 

 

Figure 12.15 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)

44

Heat & Glo • RUTHERFORD-504059-333 Rev F • 11/08

Page 44