3. Continue Adding Vent Components

!WARNING: ENSURE THAT THE FIBERGLASS GASKET SUPPLIED WITH THE FIREPLACE

SEALS BETWEEN THE FIRST VENT COMPONENT AND THE OUTER FIREPLACE WRAP.

If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops and Vent Termination.

3. Continue Adding Vent Components

!WARNING: INSTALLATION OF THIS FIRE- PLACE REQUIRES THE USE OF HEAT

SHIELD 570-290 ABOVE THE FIRST 900 ELBOW IN THE VENTING SYSTEM.

To Install the Heat Shield:

1.Determine if the heat shield is required. Do so by mea- suring the vertical distance between the top horizontal surface of the elbow to any combustible surface above. If the distance is more than 4 inches, the heat shield is NOT required. If it is 4 inches or less, the heat shield IS REQUIRED. Install per the following steps. See Figure 20.

COMBUSTIBLE

SURFACE

3” MIN.

(76mm)

HEAT

SHIELD

Figure 20

2.Fasten the shield in place using the four pilot holes pro- vided in the part. The shield should be oriented such that the 13 1/8 inch dimension (longest dimension) is run- ning in the same direction the elbow is pointing. The shield should be centered directly above the elbow, and positioned so that it creates a 1/2 inch airspace between the shield and the combustible surface. See Figure 21.

If the combustible materials are not in place at the time of install the elbow heat shield may be screwed to the exhaust pipe (see Figure 22). Cut the tabs as shown and bend down. Secure the heat shield to the pipe main- taining 3” to 4” between the pipe and shield.

SCREW

3”

(76mm)

Figure 22

Refer to Cinch Pipe and Termination Cap installation in- structions.

Continue adding vent components, locking each succeed- ing component into place.

Ensure that each succeeding vent component is secure- ly fitted and locked into the preceding component in the vent system.

90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an el- bow does not end up in a locked position with the pre- ceding component, attach with a minimum of two (2) sheet metal screws.

4. Install Support Brackets

Refer to Cinch Pipe and Termination Cap installation in- structions.

CORRECT

INCORRECT

 

COMBUSTIBLE SURFACE

 

DIRECTION

 

UP

 

HEAT SHIELD

 

900ELBOW

Figure 21

 

22

Heat & Glo • 6000TRI-IPI, 6000TRI-SP385-901 Rev. F • 5/05